6.4
Indication for contamination during run mode
7
Process data structure
8
Troubleshooting
8022198.1G8F/2023-03-29 | SICK
Subject to change without notice
Table 9: Indication for contamination
no contamination:
→ continue to set up / use
sensor
IO-Link
Process data
Bit 0 / Data type
Bit 1 / Data type
Bit 2 ... 15 / Description / Data type
The Troubleshooting table indicates measures to be taken if the sensor stops working.
Table 10: Troubleshooting
LED/fault pattern
Yellow LED does not light up
even though the light beam
is aligned to the reflector and
there is no object in the path of
the beam
Green LED flashes
OPERATING INSTRUCTIONS
a little contamination:
→ sensor will still perform;
however, for optimal per‐
formance, clean front lens,
check alignment and dam‐
age of reflector too.
Cause
No voltage or voltage below
the limit values
Voltage interruptions
Sensor is faulty
IO-Link communication
O P E R A T I N G I N S T R U C T I O N S | RAY10
contamination:
→ please clean front lens
of RAY10 and reflector,
check alignment and dam‐
age of reflector too.
A new teach of RAY10 is
not required.
RAY10-xxxxxxA00
V1.1
2 byte
Byte 0: bits 15... 8
Byte 1: bits 7... 0
Q
/ Boolean
L1
Q
/ Boolean
L2
[empty]
Measures
Check the power supply,
check all electrical connec‐
tions (cables and plug connec‐
tions)
Ensure there is a stable power
supply without interruptions
If the power supply is OK,
replace the sensor
-
en