Adjustment Of Zero Point And Span - WIKA HP-2 Manual De Instrucciones

Ocultar thumbs Ver también para HP-2:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Adjustment of zero point and span

7. Adjustment of zero point and span
Only adjust the span-setting potentiometer if calibration equipment is avail-
able which has at least three times the accuracy of the pressure sensor.
EN
7.1
Preparation (figure A)
To gain access to the potentiometers, open the instru-
ment as follows:
Disconnect the electrical connection  from the
instrument.
Remove the clamping nut .
Carefully pull the instrument connector  from the
instrument.
Connect the instrument connector  to the power
supply and a display unit (e.g. ammeter, voltmeter)
according to the connection diagram.
7.2
Adjustment of zero point (figure B)
Go to the start of the measuring range.
Using potentiometer "Z", adjust the minimum output
signal (e.g. 4 mA).
7.3
Setting the span (figure B)
Go to the end of the measuring range.
Using potentiometer "S", adjust the maximum output
signal (e.g. 20 mA).
Check the zero point and if there is any deviation,
re-adjust it.
Repeat the procedure until the zero point and the
span are set correctly.
7.4
Finish the adjustment (figure A)
Disconnect the instrument connector  from the power supply and the display unit.
Carefully push the instrument connector  onto the instrument, without damaging the
wires or the seals. The seals must be clean and undamaged in order to guarantee the
given ingress protection.
Tighten the clamping nut .
After the adjustment, check that the system is functioning correctly.
Recommended recalibration cycle: Half-yearly
14
WIKA operating instructions pressure sensor, model HP-2
A
B

Publicidad

Tabla de contenido
loading

Tabla de contenido