Output Signals; Power Supply; Permissible Temperature Ranges - WIKA HP-2 Manual De Instrucciones

Ocultar thumbs Ver también para HP-2:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Specifications

Output signals

Signal type
Current (2-wire)
Voltage (3-wire)
USB

Power supply

The power supply depends on the selected output signal
4 ... 20 mA:
DC 10 ... 30 V
DC 0 ... 5 V:
DC 10 ... 30 V
DC 0 ... 10 V: DC 14 ... 30 V
USB 2.0:
DC 5 V
Load in Ω
Current output (2-wire): ≤ (power supply - 10 V) / 0.02 A
Voltage output (3-wire): > maximum output signal / 1 mA
Ingress protection (per IEC 60529)
Angular connector DIN 175301-803 A: IP 65
Circular connector M12 x 1 (4-pin):
USB connector type A:
Cable outlet:
The stated ingress protection only applies when plugged in using mating connectors
that have the appropriate ingress protection.

Permissible temperature ranges

Medium:
0 ... +80 °C
Ambient: -20 ... +80 °C
Storage: -40 ... +85 °C
CE conformity
EMC directive, emission (group 1, class B) and immunity (industrial application)
With USB signal output and strong electromagnetic disturbances in the frequency
range 650 ... 750 MHz, the accuracy can be influenced by up to 1 %.
Pressure equipment directive
RoHS directive
For special model numbers, e.g. HP-20000, please note the specifications stated on the
delivery note.
For further specifications see WIKA data sheet PE 81.53 and the order documentation.
WIKA operating instructions pressure sensor, model HP-2
Signal
4 ... 20 mA
DC 0 ... 5 V
DC 0 ... 10 V
USB 2.0
IP 67
Instrument: IP 67, connector: IP 20
IP 67
EN
9