WEG CFW700 Manual Del Usuario página 28

Ocultar thumbs Ver también para CFW700:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The keypad can be installed or removed from the inverter with or without AC power applied
to the inverter.
The HMI supplied with the product can also be used for remote command of the inverter. In
this case, use a cable with male and female D-Sub9 (DB-9) connectors wired pin to pin (mouse
extension type) or a market standard Null-Modem cable. Maximum length of 10 m (33 ft). It is
recommended the use of the M3 x 5.8 standoffs supplied with the product. Recommended
torque: 0.5 N.m (4.5 lbf.in).
Use the keypad frame accessory to assembly the keypad on the panel door or control table
(see
section 7.2 -
Accessories, or perform the drilling as shown in
NOTE!
A list of parameters is supplied with the product, for additional information
on each parameter refer to the CFW700 programming and troubleshooting
manual provided in the CD-ROM that accompanies the product or it can be
downloaded at the WEG homepage - www.weg.net.
Monitoring Mode
It is the initial state of the keypad after power up and startup screen,
with the factory default values.
The Menu is not active in this mode.
Main display, secondary display and monitoring bar show the values of
the parameters defined at P0205, P0206 and P0207.
From the monitoring mode, pressing the ENTER/MENU key will switch
to the programming mode.
Programming Mode
Level 1:
This is the first level of the programming mode. It is possible to chose
the parameter group by using the
The main display, secondary display and monitoring bar are not shown
at this level.
Press the ENTER/MENU key to go to the second level of programming
mode - parameters selection.
Press the BACK/ESC key to go back to the monitoring mode.
Level 2:
The parameter number is displayed on the main display and its value
on the secondary display.
Use the
and
keys to find the desired parameter.
Press the ENTER/MENU key to go to level 3 of the programming mode
– parameters value changing.
Press the BACK/ESC key to return to level 1 of the programming mode.
Level 3:
The parameter values is shown at the main display and the parameter
number at the secondary display.
Use the
and
keys to change the value of the selected parameter.
Press ENTER/MENU key to confirm the modification (save the new
value) or BACK/ESC key to cancel the modification (do not save the
new value). In both cases, the keypad returns to the second level of the
programming mode.
Figure 4.3: Keypad operation modes
Keypad (HMI) and Basic Programming
and
keys.
figure
A.5).
CFW700 | 21

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido