Installation and Connection

3.3.1 Conformal Installation

1) Inverters with built-in C3 RFI filter CFW700...C3...
2) Sizes A to D inverters with built-in C3 RFI filter capacitors grounding screws and size E with
J1 cable in the
position (XE1). For more information see
3) Shielded output cables (motor cables) and connect the shield at both ends (motor and
inverter) with a low impedance connection for high frequency. Use PCSx-01 kit supplied
with sizes A, B and C inverters. For sizes D and E inverters use the clamps supplied with
the product. Ensure good contact between the cable shield and the clamps. Refer to
3.4
and keep the proper separation from other cables according to
Distances. The maximum motor cable length and conduction and radiated emission levels
are presented at
table
to have a lower emission level and/or a longer motor cable length. For more information (RFI
filter commercial reference, motor cable length and emission levels) refer to
4) Shielded control cables and separate the remaining cables according to
Distances.
5) Inverter grounding according to the instructions on item
6) Grounded power supply.

3.3.2 Emission and Immunity Levels

EMC Phenomenon
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz)
Electromagnetic Radiation Disturbance
Frequency Range: 30 MHz to 1000 MHz)
Immunity:
Electrostatic Discharge (ESD)
Fast Transient-Burst
Conducted Radio-Frequency Common
Mode
Surge Immunity
Radio-Frequency Electromagnetic Field IEC 61000-4-3
Refer to
table B.5
for conducted and radiated emission levels accomplished with and without
external RFI filter. The reference model for the external filter is also presented.
18 | CFW700
B.5. Use an external RFI filter at the input of the inverter if necessary
Table 3.4: Emission and immunity levels
Basic
Standard
IEC/EN61800-3
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-6
IEC 61000-4-5
figure
A.6.
item 3.2.6 - Cable
3.2.4 - Grounding
Level
It depends on the inverter model and the motor
cable length.
See
table
B.5.
4 kV for contact discharge and 8 kV for air
discharge.
2 kV / 5 kHz (coupling capacitor) power input
cables;
1 kV / 5 kHz control cables, and remote
keypad cables;
2 kV / 5 kHz (coupling capacitor) motor output
cables.
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz).
Power supply cable, motor, control and remote
keypad (HMI).
1.2/50 μs, 8/20 μs;
1 kV line-to-line coupling;
2 kV line-to-ground coupling.
80 to 1000 MHz;
10 V/m;
80 % AM (1 kHz).
figure
table
B.5.
item 3.2.6 - Cable
Connections.