N700E INSTRUCTION MANUAL
Inverter Model
Max. Applicable motor
(Note1)
(4P, kW)
HD
Rated
capacity
(kVA)
ND
Rated input voltage
Rated output voltage
Rated output current
(A)
Weight (Kg)
Protection Design
Footnotes for the preceding tables
Note 1. The applicable motor refers to HYUNDAI standard 3-phase motor(4-pole).
To use other motors, care must be taken to prevent the rated motor current(50/60Hz)
from exceeding the rated output current of the inverter.
Note 2. The output voltage decreases as the main supply voltage decreases
(except for use of the AVR function).
In any case, the output voltage cannot exceed the input power supply voltage.
(3) Common specifications for 200V/400V class
Inverter model
(Note3)
Control system
Output frequency
(Note4)
range
Frequency
(Note5)
accuracy
Frequency resolving
power
Voltage/frequency
characteristic
Overload current rate
Acceleration/Decelerati
on
DC Braking
Operator
Freque
Extend
ncy
signal
Operator
Run/
Extend
Stop
signal
Intelligent input
terminal
1100HF/
1320HFP
HD
110
ND
132
380V
142.8
480V
180.4
380V
159
480V
191
(Note2)
Three-phase 380~480V (corresponding to input voltage)
HD
217
ND
230
60
Common specifications for all model
Space vector modulation PWM system
0.01∼400Hz
Digital command ±0.01% for Max. frequency, analog frequency ±0.1% (25±10℃)
Digital setting : 0.01HZ, Analog setting : Max. frequency / 1,000
V/f control (constant torque, reduced torque), free V/f control
Heavy Duty(150%, 60sec), Normal Duty(120%, 60sec)
0.1∼3000.0 sec (Director, curve setting)
On starting and decelerating by stop command, inverter operates under operation
setting frequency. Or inverter operates with external input (Breaking power, time,
frequency can be set.)
Setting by up/down key
Input voltage : DC0∼+10V (Input impedance 10KΩ)
Input current : 4∼20mA (Input impedance 200Ω)
Run / Stop key (Forward / Reverse function mode)
Forward run / stop (1a connect, 1b selection possibility)
FW(Forward), RV(Reverse),
CF1~4(Multi-speed bit 1~4), RS(reset),
AT(Analog input current/voltage selection signal), USP(USP function)
EXT(external trip), FRS(free-run stop), JG(jogging),
SFT(software lock), 2CH(2
1320HF/
1600HF/
1600HFP
2000HFP
132
160
160
200
171.1
195
216.2
230
204
245
245
285
Three-phase 380~480V±10%, 50/60Hz±5%
260
300
285
370
60
110
IP00
nd
acceleration)
10-2
2200HF/
2800HF/
2500HFP
3200HFP
220
280
250
320
270
340
315
400
305
390
360
470
415
525
450
600
110
170
3500HF/
3800HFP
350
375
430
500
460
550
656
680
170