N 00E
7
MANUAL
DE
INSTRUCCIONES
Jogging Command [JG]
• When the terminal [JG] is turned on and
the Run command is issued, the inverter
outputs the programmed jog frequency
to the motor. Use a switch between
terminals [CM1] and [P24] to activate
the JG frequency.
• The frequency for the jogging operation is
set by parameter A26.
•Set the value 1(terminal mode) in A02(Run command)
• Since jogging does not use an acceleration ramp, we recommend
setting the jogging frequency in A26 to 5Hz or less to prevent tripping.
The type of deceleration used to end a motor jog is selectable by programming function A27 The options are:
0 : Free-run stop (coasting)
1 : Deceleration (normal level) and stop
2 : DC braking and stop
Option
Terminal
Code
Symbol
6
JG
Valid for inputs:
Required setting
Notes:
• No jogging operation is performed when
the set value of jogging frequency A26 is
smaller than the start frequency B10 or the
value is 0Hz.
• Be sure to stop the motor when switching
the function [JG] on or off.
Input
Function Name
State
Jogging
OFF
C01,C02,C03,C04,C05,C06
A02, A26, A27
[JG]
Terminal
RUN
[FW,RV]
Moter
Speed
Inverter is in Run Mode, output to
ON
motor runs at jog parameter
frequency.
Inverter is in Stop Mode.
Example:
5-8
Description
(A27)