Displays On The Ed05 Pressure Regulator With Integrated M12 Plug - Aventics ED05 Instrucciones De Servicio

Válvula reguladora de presión
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 179
9
8
00126345
AVENTICS | ED05 | R414002533–BAL–001–AG
(also set point = 0). In this case, it sends a 24 V voltage signal via
pin 4 of the integrated XPC plug, M12.
This signal can be used e.g. by the controller to enable additional
process steps.
8.1.2 Displays on the ED05 pressure regulator with
integrated M12 plug
ED05 pressure regulator with integrated M12 plug has two
LEDs:
Green POWER LED (9)
Green STATUS LED (8)
Tabelle 8:
Meaning of the
POWER LED
Off
Flashing green
Illuminated green
1)
The voltage at the ED05 pressure regulator plug is decisive
Tabelle 9:
Meaning of the
STATUS LED
Off
Flashing green
Illuminated green
If the green POWER (9) and the green STATUS (8) LED are
illuminated, the ED05 pressure regulator is operating correctly
and the supply voltage is within the tolerance range.
Both LEDs will flash for approx. 2 s during the initialization
phase (switching the supply voltage on).
Controlling the ED05 pressure regulator
POWER
LED
Meaning
No voltage present
Low voltage (< 19.2 V)
Ready for operation
STATUS
LED
Meaning
Set point = 0
Set point > 0
Pressure outside the tolerance of
±200 mbar
Set point > 0
Pressure inside the tolerance of
±200 mbar
73
1)

Publicidad

Tabla de contenido
loading

Tabla de contenido