Calculation of filter current
I filter [A] =
Uln * √3 * ηf * ηl * ηm
Example:
Rated motor power Pm
Motor efficiency ηm
Mains voltage Uln
Mains frequency
Inverter efficiency ηl
Passive filter efficiency ηf
Filter current
The rated current of the chosen filter must be ≥ the filter current calculated above:
RHF-A/B 29-400-50-20-A
10.4.2 Connection diagrams
Figure 10.4.1: RHF-A-... and RHF-B-... models
F1
3
5
1
K1M
2
4
6
X2.1
X2.2 X2.3
L1
L2
ADV200
U
W
V
M
3~
E
ADV200 • Guía rápida de instalación - Especificaciones y conexión
Pm
18.5 [kW]
95%
400 [V]
50 [Hz]
98%
99.0%
29.0 [A]
X3.1 X3.2 X3.3
RHF-A/B-...
A
B
X4.1 X4.2 X4.3
Auxiliary circuit
(Pulse lock)
L3
L1
L2
L3
N
PE
K2M
Capacitor disconnect
(optional)