Descargar Imprimir esta página

Hitachi RPI-2.0FSN3E Manual De Instalación Y Funcionamiento página 16

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
6 Electrical wiring
DSW6
ON
1 2 3 4 5 6
Here is set DSW6 and rSW1 before shipment up to 63 can be set.
Ex. Setting nº16
ON
1 2 3 4 5 6

 
DSW3: Capacity Code Setting
No setting is required, due to setting before shipment. This dip switch
is utilized for setting the capacity code which corresponds to the Horse
Power of the indoor unit.
HP
1.8
ON
ON
Setting
Position
1 2 3 4
HP
3.0
ON
ON
Setting
Position
1 2 3 4

 
DSW5 and RSW2: Refrigerant Cycle No. Setting
Setting is required. Setting position before shipment in
DSW5
ON
1 2 3 4 5 6
Here is set DSW5 and rSW2 before shipment up to 63 can be set.
Ex. Setting 5 system
ON
1 2 3 4 5 6
All pins are OFF
RSW1
RSW1
2.0
2.3
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
4.0
5.0
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
RSW2
RSW2
Fix to 5
10
PmmL0230A rev.1 - 06/2011

 
DSW4: Unit Model Code Setting
No setting is required. This switch is utilized for setting the model code
which corresponds to the indoor unit type.
Indoor Unit Model
rPI

 
DSW7: fuse Recover
In case of applying high volt-
age to the terminal 1,2 of TB1,
the fuse on the PCB1(m) is
cut. In such a case, firstly
correct the wiring to TB1 and
then turn ON #1 (as showing
beside)

 
DSW7: Remote Control Selection
2.5
No setting is required. Setting
position before shipment is all
OFF (PC-ArT remote Con-
trol Switch Selected).
6.0
N O T E
The mark "
" indicates position of dips switches. Figures show set-
ting before shipment or after selection.
DSW4 Setting
ON
1 2 3 4
ON
1 2
ON
1 2

Publicidad

loading

Este manual también es adecuado para:

Rpi-2.5fsn3eRpi-3.0fsn3eRpi-4.0fsn3eRpi-5.0fsn3eRpi-6.0fsn3e