TEMP. CURVE SET
LOW TEMP. FOR ZONE-A COOL
HIGH TEMP. FOR ZONE-A HEAT
LOW TEMP. FOR ZONE-B COOL
LOW TEMP. FOR ZONE-A HEAT
ZONE B here means ZONE 2.
6.3 Domestic Hot Water (DHW)
DHW mode typically consists of the following
1)
DISINFECT
2)
DHW PUMP
6.3.1 DISINFECT
The DISINFECT function is used to kill the IegioneIIa. In disinfect function the tank temperature
will reach 55℃~75℃ forcedly. The disinfect temperature is set in FUNCTION PARAMETER SET.
See "FUNCTION PARAMETER SET" » "DHW MODE SET" » "Tx" in "Installation and owner's
manual".
Go to "
" » "DHW ADDITIONAL FUNCTION" »"DISINFECT". Press "
page will appear:
Use"
"、 "
"、 "
setting "CURRENT STATE" and "OPERATION" and "START".
If the CURRENT STATE is set to ON, the disinfect function will active, but it is only once effective.
If the OPERATE DAY is set to FRIDAY and the "START" is set to "Y and 23:00", the disinfect function
will be active on 23:00 Friday.
If the disinfect function is running, the icon will appear on the home page.
4
6
4
3
"、 "
" to scroll and use "
+
"、 "
" to adjust the parameters when
18
"、"OK". The following