Operation

Note! Connect the LC-151 to a positive Voltage output of 9.6 -16Vdc source.
Use only a listed power limited source.
The detector shall be provided with minimum of 4 hours of standby power from either a
listed compatible control unit or power supply.
The detector begins a 30 second warm up period once connected to power.
If the LEDs are enabled, they will sequentially flash from left to right for the duration of the 30
seconds warm up period.
Once the warm up period is complete, the detector is ready for use.

10 Test procedure

Walk Test
IMPORTANT NOTE: Once installed, the unit should be thoroughly tested to verify proper
operation and coverage. After installation, the unit should be tested annually by the
installer. The end user should be instructed on how to perform a weekly walk test.
Make sure LEDs control is set to "ON"
Ensure the detector has completed the 30 second warm up period before walk testing.
Make sure that the protected area is cleared of all people.
Create motion in the entire area where coverage is desired by walking perpendicular to the
detection pattern.
Look at the LEDs whenever motion is detected - all LEDs are turned ON.
Allow 5 sec. between each test for the detector to stabilize.
Walk across the entire area where coverage is desired. Should the coverage be incomplete,
readjust sensitivity or relocate the detector.
Once coverage is as desired the LEDs should be disabled.

11 Accessories

Device
Outdoor Mounting bracket
PIR Corridor/Long Range Lens
36kg (80lb) PET Filter
Part Number
LC-B1-15X
LC-L1-15X