5.8 CYCLING function
set
esc
1. Press
and
together at the same time to enter general menu "PAr" .
set
2. Press
to enter on menu .
to fi nd parameter " C4C".
3. Use the arrows
or
set
4. Press
to enter on menu .
to fi nd parameter " C7".
5. Use the arrows
or
set
6. Press
to choose:
ON : continuous;
OFF: cycling.
set
7. Press
to confi rm.
esc
8. Press
to exit.
esc
set
PAr
esc
CF9
C37
OFF
"C37" show the % of energy saving.
English
set
C4C
set
esc
C7
set
esc
On
5.9 Alarm management
set
esc
1. Press
and
together at the same time to enter general menu "PAr" .
set
to enter on menu " CF9".
2. Press
3. Use the arrows
or
PARAMETER
Alarm relay management
OFF = alarm; On = warning /alarm
In an alarm/warning situation, follow the procedure below:
set
1. Press
to enter menu of direct parameters.
2. Use the arrows
or
set
3. Press
to see alarm code:
ALARM LIST
H.C. Cod. Description
10 LD Low dew point
11 LT Low evaporation temperature
13 HT2 High discharge temperature
18 HP High pressure
19 LP Low Pressure
21
PI Compressor Thermal protect.
22 PH Inverted phases
(H.C=History code)
PSE 325-1000 60Hz
to fi nd parameter " CFJ1 ".
CODE
TYPE
CFJ1
D
to fi nd parameter " AL".
set
AL
HiSt
set
esc
.....
Hd
WARNING LIST
Reset H.C. Cod.
Description
M
1/2 FBO/2 B0/2 sensor warning
M
3/5 FB5/8 B5/8 sensor warning
M
7
FP1
PI sensor warning
M
24
DRE
Condensate drain warning
M
9
HD
High dew point warning
M
12
HT1
High discharge temp.
M
14
HB5
High suction compres. temp.
20
HP1
High pressure
25
SR
Maintenance
DEFAULT
OFF
Reset
A
A
A
A
A
A
A
A
A
8/20