Descargar Imprimir esta página

Mitsubishi Electric TRANE CITY MULTI TPKFYP LM140 Serie Manual De Instalación página 8

Ocultar thumbs Ver también para TRANE CITY MULTI TPKFYP LM140 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Installing the refrigerant piping
B
en
7
A
Fig. 4-3
A
B
C
Fig. 4-4
4.3. Refrigerant piping (Fig. 4-3)
Indoor unit
1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit's liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. The portion where the insulation material is joined is sealed by taping.
A Site-side refrigerant piping
B Unit side refrigerant piping
4.3.1. Storing in the piping space of the unit (Fig. 4-4)
1. Wrap the supplied felt tape in the range of the refrigerant piping which will be
housed within the piping space of the unit to prevent dripping.
2. Overlap the felt tape at one-half of the tape width.
3. Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe
B Liquid pipe
C Felt tape 3

Publicidad

loading