3 CONDUIT HOLE
The VERIFEYE 61N00 is shipped without conduit holes. They will need to be cut on the left side, right
side, and/or the top of the enclosure. See the below drawings for recommended conduit hole locations.
1. Open the enclosure door, unscrew the two right ride screws, and lift the metal plate.
2. Cut the conduit holes only in the locations where conduit fittings will be installed. Conduit hole
templates can be found within the black bag that comes in the box.
3. To maintain the enclosure's environmental rating, the installer must use conduit hubs/fittings with
the same environmental rating as the enclosure. (Fittings not supplied by Leviton)
4. Maintain spacing of at least ½ in. between conduit hubs/fittings and uninsulated live conductors.
5. Use "Grounding" conduit fittings with built-in set screws. Run insulated copper conductors,
16AWG or thicker, from fittings to spar ground terminal blocks.
6. Route incoming voltage conductors at least ¼ in. away from current sensor and signal conductors.
Route current sensor conductors at least ¼ in. away from communication conductors.
7. Use cable ties to secure conductors to each other and to maintain spacing.
LEFT SIDE
7
5
16 (Centered)
Alternative conduit hole location for
1/2 in., 3/4 in., or 1 in. conduit only.
Recommended conduit
hole location for 1/2 in.,
3/4 in., or 1in. conduit only.
1
3
4
3
2
8
1
1
2
Recommended conduit
hole locations for
1/2 in. or 3/4 in.
conduit only.
Recommended Conduit Hole Locations
3
Right SIDE
Recommended conduit hole
location for 1/2 in. or 3/4 in. conduit only.
1
2
2
7
11
12
8
1
7
4
3
6
8
TOP
7
4
16 (Centered)
3
1
4
3
8

Publicidad

loading

Este manual también es adecuado para:

61n00