6.3.3
Changing the blow-out direction
As a default, the Multiboxes have been designed for a straight air throughflow. However, they can be refitted simply as a result of their
replaceable side panels.
Remove the side panel of the required direction.
"
Close the other side with this side panel (see Fig. 11).
"
NOTE (MUB T / MUB T-S)
The drain plug is secured inside the box for transport, closed with a protective cap. During installation the protec-
tive cap has to be removed, the drain plug has to be properly fixed to the thread at the bottom outside panel. After
assembly of the drain plug it has to be connected to the drain pipe provided at site.
3
Fig. 11:
MUB with various possibilities of blow-out
Legend
1
Multibox with straight air throughflow (factory assembly)
2
Multibox with angled air throughflow
3
Change of blow-out direction
NOTE
Speciality: MUB/T
The motor of the MUB/T multibox must not be in the air flow. For this reason, a straight air throughflow is not
possible.
42
1
2