Commissioning; Preconditions; Safety Elements - SystemAir Multibox MUB Serie Instrucciones De Montaje Y Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 97
8

Commissioning

8.1

Preconditions

Fitting and electrical installation have been completed expertly.
Assembly residue and foreign bodies have been removed from the fan area.
Suction and blow-out openings are free.
The safety devices have been fitted (contact protection).
The protective conductor has been connected.
The thermo-contacts (temperature monitors) have been properly connected to the motor protection switch.
The motor protection switch is functional.
The temperature monitor is functional.
The cable insert has been sealed.
Connection data correspond to the data on the name plate.
The nominal current consumption (name plate) is not exceeded.
8.2
Commissioning
WARNING
Hazard as a result of electrical voltage
Commissioning only by trained and instructed qualified personnel.
Switch the Multibox on as planned.
"
WARNING
Hazard from bursting parts
When checking the direction of rotation of the rotor, wear goggles.
Check:
"
the direction of rotation/conveying. The direction of rotation looking at the rotor always applies.
the smoothness of running.
8.2.1

Safety elements

Check secure fitting of the safety elements and protective grids.
"