Descargar Imprimir esta página

Reflex Reflexomat Basic Manual De Instrucciones Original página 25

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
The "LIS" level sensor uses a pressure load cell. This pressure pick-up is to be
installed after the primary vessel has been placed at its final position,  6.3.2
"Tank installation",  23. Comply with the following instructions:
Remove the transport securing device (squared timber) at the vessel base
of the primary vessel.
Replace this transport securing device with the pressure load cell.
Avoid shock-type loading of the pressure load cell by, for example,
subsequent alignment of the vessel.
Use flexible hoses to connect the primary vessel and the first secondary
vessel.
Use only the supplied connection sets,  6.3.2 "Tank installation",
 23.
Perform a null balancing of the filling level when the primary vessel is
aligned and fully emptied,  9.2 "Configuring settings in the controller",
 29.
Standard values for level measurements:
Primary vessel
200 l
300 – 500 l
600 l
6.4
Make-up and degassing variants
6.4.1
Function
The filling level is recorded in the primary tank by the "LIS" level sensor and
evaluated in the controller. When the water level falls below the value specified
in the controller's customer menu, the external make-up is activated.
6.4.1.1
Make-up without pump
Reflexomat Basic with solenoid valve and ball valve.
1
Reflexomat Basic
2
Solenoid valve "Fillvalve" with ball
valve
3
Reflex Fillset
ST
Dirt trap
Preferably, you should use the Reflex Fillset with integrated system separator
when using drinking water for make-up. If you don't use a Reflex Fillset, you
must use an "ST" dirt trap with a mesh size ≥ 0.25 mm for the make-up.
6.4.1.2
Make-up with pump
Reflexomat Basic with Reflex Fillcontrol Auto
Measuring range
0 – 4 bar
0 – 10 bar
0 – 25 bar
WC
Make-up pipe
LIS
Level sensor
EC
Expansion pipe
Reflexomat Basic — 13.11.2020 - Rev. A
1
Reflexomat Basic
2
Fillcontrol Auto
WC Make-up pipe
Water make-up with Fillcontrol Auto is suitable for make-up at high system
pressures of up to 8.5 bar. The "ST" dirt trap is part of the deliverables.
6.4.1.3
Make-up with softening and degassing
Reflexomat Basic and Reflex Servitec.
1
Reflexomat Basic
2
Reflex Servitec
3
Reflex Fillsoft
4
Reflex Fillset Impulse
The Reflex Servitec degassing and make-up station degasses the water from the
system circuit and the make-up water. The automatic water make-up for the
system circuit is controlled by the pressurisation system. Reflex Fillsoft
additionally softens the make-up water.
Reflex Servitec degassing and make-up station,  4.6 "Optional
equipment and accessories",  22.
Reflex Fillsoft softening systems and Reflex Fillset Impulse,  4.6 "Optional
equipment and accessories",  22.

Note!
When using Reflex Fillsoft softening systems, always install the Reflex
Fillset Impulse.
The controller evaluates the make-up quantities and signals a
required replacement of the softening cartridges.
6.5
Electrical connection
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
Ensure that the system is voltage-free before installing the device.
Ensure that the system is secured and cannot be reactivated by other
persons.
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical
engineering regulations.
All electric connections between control unit and expansion vessel are pre-
installed.
1.
Connect the mains plug to the 230 V power supply.
2.
Activate the system.
The electrical connection is completed.
6.5.1
Terminal diagram
Installation
ST
Dirt trap
EC Expansion pipe
LIS Level sensor
ST
Dirt trap
WC Make-up pipe
LIS
Level sensor
EC
Expansion pipe
English — 25

Publicidad

loading

Este manual también es adecuado para:

888240088826108882200888221088825108882410