Selecting and changing parameters
1.
Use "OK" (5) to select the parameter.
2.
Use the "▼" (7) or "▲" (9) arrow keys to change the parameter.
3.
Use "OK" (5) to confirm the parameter.
4.
Use the "▼" (7) or "▲" (9) arrow keys to switch to a different menu
option.
5.
Use "Quit" (11) to switch to a different menu level.
9.2
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
System-specific values can be corrected via the customer menu. In the course of
initial commissioning, the factory settings must first be adjusted for the system-
specific conditions.
Note!
For a description of the operation, 9.1 "Operator panel", 28.
All grey marked menu items must be reviewed during commissioning.
Press "Manual" to switch to manual operation.
Press "Menu" to display the first main menu option "Customer menu".
Indication on the
Meaning
display
Customer menu
Switch to the next main menu option.
Language
Standard software in various languages.
Time:
Adjust the "Hour", "Minute", and "Second" display when
each begins to flash.
This time is used for entries in the fault memory.
Date:
Adjust the "Day", "Month", and "Year" display when each
begins to flash.
This date is used for entries in the fault memory.
1 % / 1.7 bar
The controller checks whether the level sensor signal
matches the value entered for the "RG" primary vessel in
Null balancing?
the controller, 7.3 "Modifying the controller's start
routine", 27.
Note!
The "RG" primary vessel must be completely
empty.
0 % / 0 bar
One of the following messages appears on the display:
Null balancing
•
Null balancing concluded successfully
successfully
Confirm with the "▼" button.
concluded!
•
Empty vessel and repeat the process
Confirm with "OK".
0 % / 0 bar
This message appears when null balancing has failed.
Select "Yes" or "No" on the display.
Cancel null
balancing?
•
YES: The "RG" primary vessel is empty and the
device is installed as per the instructions. If null
No
balancing is still not possible, cancel with "Yes".
Contact your Reflex Customer Service.
•
NO: Check the prerequisites for the commissioning,
7.1 "Checking the requirements for
commissioning", 26.
The controller's start routine has been restarted.
Confirm the selection of "yes" or "no" with "OK".
Min.op.pressure
Enter the value for the minimum operating pressure.
01.8 bar
Note!
Calculation of minimum operating pressure,
7.2 "Reflexomat switching points", 27.
Make-up
Switch to the "Make-up" main menu.
•
Press "OK" to open the menu.
•
Use the "▼▲" buttons to open the sub-menu.
Make-up: ON
If the water content is below the specified vessel size,
add water, 7.3 "Modifying the controller's start
at: 08 %
routine", 27.
•
If an automatic make-up device (Fillcontrol for
example) is installed, make-up will be actuated
automatically; otherwise the make-up must be
manually activated.
Indication on the
display
Make-up: OFF
at: 12 %
Max. make-up time
010 min.
Max. make-up
cycles
003 / 2 h
With water meter.
YES
Make-up volume
000020 l
Max. make-up
volume
000100 l
With softening
YES
Disable make-up?
YES
Hardness reduction
10 °dH
Cap. soft water
05000 l
Remaining cap. soft
w.
000020 l
Reflexomat Basic — 13.11.2020 - Rev. A
Meaning
Terminate the water make-up when the specified vessel
size is exceeded.
•
If an automatic make-up device is installed, make-
up will be shut off automatically; otherwise the
make-up must be manually deactivated.
•
If you have selected "No" for automatic make-up,
the system will not return any further queries
about the make-up.
Pre-selected time for a make-up cycle. Upon expiry of
this set time, the system interrupts the make-up and
returns the "Make-up time" fault message.
If the set number of make-up cycles is exceeded within
two hours, the system interrupts the make-up and
returns the "Make-up cycles" fault message.
•
YES: FQIRA+ contact water meter is installed,
4.6 "Optional equipment and accessories", 22.
This is the prerequisite for the make-up volume
monitoring and the operation of a softening
system.
•
NO: A contact water meter is not installed
(standard model).
Only displayed if "YES" has been set in the "With water
meter" menu option.
•
Use "OK" to delete the counter.
–
Press "YES" to reset the value displayed to
"0".
–
Press "NO" to retain the displayed value.
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
•
When the set volume is exceeded, the system
interrupts the make-up process and returns the
error message "Max. make-up volume exceeded".
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
•
YES: Further queries follow about softening.
•
NO: The system does not offer more queries
regarding the softening process.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
YES: The system stops the make-up process when
the set soft water capacity is exceeded.
•
NO: The system does not stop the make-up
process. The system displays the "Softening"
message.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Hardness reduction is calculated from the
difference of the overall water hardness GH
and the target water hardness GH
Hardness reduction = GH
actual
Enter the value in the controller. Consult the
manufacturer information for third-party products.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
The attainable soft water capacity is calculated from the
type of softening used and the specified hardness
reduction.
•
Fillsoft I, soft water capacity ≤ 6000/hardness red. l
•
Fillsoft II, soft water capacity ≤ 12000/hardness
red. l
Enter the value in the controller. Consult the
manufacturer information for the values of third-party
products.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Available soft water capacity.
Controller
actual
.
target
-GH
l °dH
target
English — 29