Indicating Phase Rotation (RST)
V
AC
200
2000m
200m
RST
Hz
200M
20M
k
Function
Frequency Range
Phase
Rotation
Indicator
To Determine Phase Rotation (RST):
This test function correctly identifies each of the 3-Phases in a
power panel as R, S, T. Note: The displayed numerical value
has no meaning when performing this procedure. Maximum 3
phase voltage allowed in this mode is 500 VAC.
1. Turn power off to the circuit that is to be tested.
2. Place the function switch on the meter to "RST."
3. Plug the test leads into the meter inputs labeled as R, S, T
in the diagram above. Note that test lead colors are insignif-
icant.
4. Attach the three test leads to each of the 3-Phase cables in
any order.
5. Turn the power on.
6. If all three supply lines have power, the meter will indicate a
R, S, T (in the upper left corner).