Descargar Imprimir esta página

Emerson AVENTICS AF2 Instrucciones De Montaje página 21

Ocultar thumbs Ver también para AVENTICS AF2:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 46
• Check the product functions.
9.2 Cleaning
9.2.1 General requirements
Cleaning intervals
• The system owner specifies the cleaning intervals in line with the ambient
conditions at the operating site.
Aids
• Only clean the product with damp cloths.
• Only use water for cleaning and a mild detergent, if necessary.
9.2.2 Procedure
1. Close all openings with suitable safety devices so that no cleaning agent can
enter into the system.
2. Remove all dust deposits from the product and the adjacent system parts.
3. If necessary, remove other production-related deposits from the product and
the adjacent system parts.
9.3 Maintenance
In normal ambient conditions, the product is maintenance-free.
9.4 After service
If no damage has been detected and the operator has not reported any malfunc-
tions, the product can be reconnected to the power supply and put back into op-
eration.
10 Disassembly and exchange
Disassembly is only required if the product has to be exchanged, installed in a dif-
ferent location or disposed off.
10.1 Basic requirements
10.2 Preparation
1. Close off dangerous areas.
2. Make sure the system or system part is not under pressure or voltage.
DANGER! Slowly exhaust the system to avoid uncontrolled movements of the
system components.
3. Protect the system against being restarted.
4. Allow product and adjacent system parts to cool down.
5. Wear PPE.
6. Loosen and remove all connections.
7. Remove the flow sensor from the pressure connection using an open-end
wrench (thread connection) or pull it straight out of the push-in fitting.
11 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
12 Troubleshooting
12.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections
• Settings. See
g 13. Technical
AVENTICS™ AF2 | R412026496–BAL–001–AC | English
data.
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
12.2 Malfunction types
Malfunctions of classification Info
Message
Description
Simulation active
Simulation active (output sig-
nal or process variable).
Flow low Info
Info: MBE -5 %.
Flow high Info
Info: Standard MBE +5 %.
Temperature high
Temperature too high.
Energy Counter off - Air only Medium = Air
Formula for energy counter
only stored for air, therefore
without function.
Voltage low for Q1/2
Voltage at Q1/2 too low.
Voltage low for Q2/a, Qa
Voltage at Q2/a, Qa too low.
Voltage low for IO-Link
Voltage too low for IO-Link.
Q1 Config out of Range
Switching points parameter-
ized outside the measurement
range.
Q2 Config out of Range
Switching points parameter-
ized outside the measurement
range.
Qa Config out of Range
Switching points parameter-
ized outside the measurement
range.
Malfunctions of classification Warning
Message
Description
No MQTT Connection
No connection possible to the
MQTT broker.
Q1/2 Overtemp
Driver overload for switch out-
put Q1/Q2.
Q1 Shortcut
Short circuit at Q1.
Q2 Shortcut
Short circuit at Q2.
Q2/a Overload
Q2/a: No current flow.
Qa Overload
Qa: No current flow.
Q2/a OverTemp
Q2/a: Overtemperature of the
output driver.
Qa OverTemp
Qa: Overtemperature of the
output driver.
Q2 PulseConfig
Implausible configuration of
the Q2 pulse output.
Flow high Warning
Warning: Extended MBE +5 %. Reduce the extended MBE to
Pressure low
Pressure too low.
Pressure high
Pressure too high.
Temperature low
Temperature too low.
g 4.3 Returning the
product.
Remedy
-
Increase MBE to the specified
value.
Reduce the standard MBE to
the specified value.
Reduce the temperature to
the specified value.
-
Adjust voltage to the specified
value.
Adjust voltage to the specified
value.
Adjust voltage to the specified
value.
Parameterize switching points
within the measuring range.
Parameterize switching points
within the measuring range.
Parameterize switching points
within the measuring range.
Remedy
• There is a problem in the
MQTT configuration:
Check if broker, port or au-
thentication are invalid.
• There is a problem in the
Ethernet configuration:
Check network settings.
• Reduce the load on the
switch outputs.
• Ensure that specified val-
ues for ambient tempera-
ture are maintained.
Eliminate short circuit.
Eliminate short circuit.
• Check whether line is
properly connected.
• Check whether load resis-
tance is too high.
• Ideal: load of 500 Ω
• Check whether ambient
temperature is too high.
• Reduce pulse width.
• Increase pulse value.
the specified value.
Increase pressure.
Reduce pressure.
Increase the temperature to
the specified value.
21

Publicidad

loading