Commissioning
NOTICE
Damage to property due to lubricants!
Seals can be destroyed by the use of greases or oils.
!
Do not use greases or oils during mounting.
!
If necessary, flush dirt particles and grease and oil residues out of the
pipework.
!
When selecting the operating medium, observe the current state of the art.
!
If the operating medium is contaminated, install a strainer in the supply
pipe.
The valve can be installed in any position.
f
Make sure that the product and the pipework are free from contamination.
f
Mount the valve so that the flow is in the direction of the arrow. (Note the
marking on the body.)
f
Install the product free of tension.
f
Make sure that the valve remains easily accessible.
1
Fit the shutoff valve into the pipe.
2
Screw the shutoff valve on tightly.
7.
Commissioning
1
Fill the heating system.
2
Vent the heating system.
3
Carry out a leak test according to DIN EN 1264.
8.
Dismantling and disposal
When the product reaches the end of its service life or has an irreparable defect,
it must be dismantled and disposed of in an environmentally friendly manner or
the components must be recycled.
3 8
1000086521_10242265 000 00