Descargar Imprimir esta página

baltur TBG 35 220/60 Manual De Instrucciones De Uso página 74

Publicidad

Idiomas disponibles

Idiomas disponibles

ENGLISH
Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
Analyse combustion gases and check emissions values.
If it is necessary to clean the outside of the combustion head, take out
its components according to the procedure described:
Undo the fastening screws (6) and remove the lid (11).
Make sure that the mobile plate (23) is fastened by the screw (8).
Once the maintenance operations have been completed, this
will make it possible to return the mixer assembly to the same
position it was in last time it was adjusted.Loosen the screw (24),
which anchors the unit's forward movement rod to the mobile
plate.
After having loosened the nut (9) remove the blocking screw (12)
of the mixer unit.
Completely remove the mixing unit, pulling it out in the direction
shown by arrow (18), after pulling the ignition and ionisation
cables (14) out of their electrodes (figure 4).
Having completed the maintenance work, replace the combustion
head, following in reverse order the operations described above,
after having checked the correct position of ignition and ionisation
electrodes.
32 / 40
0006160660_202402

Publicidad

loading

Este manual también es adecuado para:

17325410