and off
repeatedly.
Buzzer beeps
continuously
and red LED is
on.
Fault code 07
Fault code 05
Fault code 02
Fault code 03
Fault code 01
Fault code 06/58
Fault code
08/09/53/57
Fault code 51
Fault code 52
Fault code 55
EN
Overload error.
The inverter is
overloaded 110%
and time is up.
Output short
circuited.
Temperature of
internal converter
component is over
120
o
C (only
available for
1000VA/2000VA
models)
Internal
temperature of
inverter
component is over
100
o
C.
Battery is
overcharged.
The battery
voltage is too high.
Fan fault.
Output abnormal
(inverter voltage
below 190VAC or
higher than
260VAC).
Internal
component failed.
Overcurrent or
surge.
Bus voltage is too
low.
Output voltage is
Reduce the
connected load by
switching off some
equipment.
Check if wiring is
connected well and
remove abnormal
load.
Check whether the
air flow of the unit is
blocked or whether
the ambient
temperature is high.
Return for service
repair.
Check if spec and
quantity of batteries
are meet
requirements.
Replace the fan.
1. Reduce the
connected load.
2. Return for service
repair.
Return to service
repair.
Restart the unit, if
the error happens
again, please return
for service repair.

Publicidad