adjusted
according to
connected
load power
(only
available in
4000VA
model)
Battery
33
equalization
Battery
34
equalization
voltage
Battery
35
equalized
time
Battery
36
equalized
timeout
Equalization
37
interval
EN
Solar
power
disable:
If "flooded" or "User-defined" is selected in program
05, this program can be set up.
1000VA/2000VA default setting: 29.2V
Setting range is from 25.0V to 30V. Increment of each
click is 0.1V.
4000VA default setting: 58.4V
Setting range is from 50V to 60V. Increment of each
click is 0.1V.
60 min (default)
120 min (default)
30 days (default)
power + connected load
power.
If selected, the solar input
power will be the same to
max. battery charging
power no matter how
balance
much loads are
connected. The max.
battery charging power
will be based on the
setting current in
program 02.
(Max. solar power = Max.
battery charging power)
Setting range is from 5
min to 900 min.
Increment of each click is
5 min.
Setting range is from 5
min to 900 min.
Increment of each click is
5 min.
Setting range is from 0 to
90 days.
Increment of each click is

Publicidad