Voc
Short circuit current
Isc
Maximum PV module numbers in series: 3
PV module numbers in parallel: 3
Total PV module numbers: 9
The 2000VA inverter as an example to set proper PV modules. After considering
Voc of PV modules not exceeds 80V DC and max. Vmpp of PV module close to 80V
DC or within 30~115V DC, we can choose PV module with below specification:
Maximum
(Pmax)
Max. power voltage
Vmpp
Max. Power current
Impp
Open circuit voltage
Voc
Short circuit current
Isc
Maximum PV module numbers in series: 2
PV module numbers in parallel: N/A
Total PV module numbers: 2
Follow below steps to implement PV module connection:
a) Remove insulation sleeve 10mm for positive and negative conductors.
b) Check correct polarity of connection cable from PV modules and PV input
connectors. Then connect positive pole ( + ) of connection cable to positive
pole ( + ) of PV input connector. Connect negative pole ( - ) of connection
cable to negative pole ( - ) of PV input connector.
14.01 A
power
550W
41.28 V
13.33 A
49.8 V
14.01 A
EN
total PV module numbers
3
Max PV module numbers
in series 1→41.28x1≒
30~115