Preparation for installing the unit
5.2. Environmental conditions
Environmental conditions must be taken into account when choosing the location of the unit.
Maximum relative humidity without condensation
Ask Ingeteam. Low temperature kit.
(1)
The operation of the unit at temperatures greater than 40ºC should only occur occasionally and not permanently. The unit can enter
(2)
reduced performance mode (derating).
Ingeteam is not responsible for the consequences to the unit resulting from operating it at temperatures higher than 40ºC.
At altitudes higher than 2,000m, please contact Ingeteam.
(3)
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, it is necessary to monitor these units once they
have been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit. To remove condensation, apply a flow of hot air at a
maximum temperature of 55ºC.
INFO
Ingeteam does not guarantee the proper operation of the equipment if the operation conditions for which it has
been designed are not fulfilled.
300000772 - Monterings- och bruksanvisning
Environmental conditions
Minimum temperature
Minimum surrounding air temperature
Maximum operating temperature
Altitude
-35ºC
(1)
-35ºC
(1)
55ºC
(2)
95 %
2000 m
(3)