Descargar Imprimir esta página

Ingeteam RAPID 60 Manual De Instalacion Y Uso página 40

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Ingeteam
If you use a different anchoring system, check that the solution provided complies with the conditions
initially defined in this document.
Minimum thickness of the concrete pad: 300 mm.
The dimensions of the inspection chamber of the pad are shown in the following figure.
Minimum depth of the inspection chamber of the pad of 200 mm. This allows a standard cable of 240
mm
with a turning radius of 135 mm (e.g. EXZHELLENT XXI 1,000 V RZ1-K (AS) 0.6-1 kV).
2
If the radius of curvature of the selected cable is greater than the radius of curvature of 135 mm, the
depth of the inspection chamber must be greater.
The minimum depth of the anchoring system must be inserted a minimum of 45 mm into the concrete.
This anchoring system must comply with the following parameters:
Minimum tensile strength: 7.7 kN. Security coefficient 1.5.
40
726
200
258
Installing the unit
300000772 - Monterings- och bruksanvisning
134

Publicidad

loading

Este manual también es adecuado para:

Rapid 60 oneRapid 60 duoRapid 60 trio