13. Maintenance
The maintenance described below lists a series of minimum measures necessary to maintain the charger in good
working condition. Please consult Ingeteam preventive and predictive general maintenance if you wish to extend
the service life of the charger.
CAUTION
The recommended maintenance tasks must be carried out at least annually, except where otherwise stated.
13.1. Safety conditions
DANGER
All work must be carried out without voltage. If you need to carry out work close to directly accessible live
elements, you must do so according to the specifications in a work instruction or similar document.
Keep the doors closed when you are not working in the cubicle.
Keep polycarbonate guards and grilles (protections) in place at all times for elements with directly accessible
live parts.
Pay special attention to any parts that may protrude from the unit, such as rods and/or metal edges.
Do not wear rings, chains, watches, baggy clothes, loose hair or any element that may become trapped. Take
care when using gloves or cleaning cloths.
In the event of poor lighting, use auxiliary lighting devices.
CAUTION
The entire manual must be read and understood in full prior to manipulating, installing or operating the unit.
Any work carried out that implies a modification of the original electrical arrangements must be proposed and
accepted in advance by INGETEAM.
13.2. Condition of hoses and charging connectors
Check the condition of the hoses and connectors. They should not have dents or cuts. Check the proper operation
of the connectors.
Check the correct operation of the retractable system. Check the hoses are in good condition and the springs bend
smoothly.
Check the condition of the hose holder. Check that the polycarbonate guards are attached and that there is no dirt
or damp.
13.3. Condition of the housing
You must carry out a periodical inspection of the condition of the enclosure, verifying the condition of the locks
and doors, as well as the anchoring of the units to the ground. In addition, you must check the condition of the
housing and the absence of dents or scratches that might degrade the housing or cause it to lose its protection
classification. If these types of defect are noticed, the affected parts must be repaired or replaced.
13.4. Condition of cables and terminals
Check that the power circuit connections have the correct tightening torque.
Check that the power cables look in good condition and there are no signs of wear or overheating.
62
300000772 - Monterings- och bruksanvisning
Maintenance