Technical description
Setting the lower current saturation limit (mode 11)
•
The lower current saturation limit is set in mA and confirmed by pressing the
M button; this takes you to the next mode (mode 12)
•
The setting range is between 3.6 mA and 3.8 mA
Setting electrical damping (mode 12)
The time response of the unit is determined by adjustable electrical damping. Damp-
ing can be adjusted to between 0.1 and 100 s at intervals of 0.1 s.
Following parameterization and confirmation with the M button, the unit goes to
mode 1.
48
Operating instructions
SITRANS P, ZD series
A5E00249308-01