Note!
The weight measuring cell is not resistant to water hammer; also it must
not be painted!
7.4
Switching and make-up variants
7.4.1
Function
The current filling level is recorded in the primary tank by the "LIS" level sensor
and evaluated in the controller. The value for the minimum filling level is
specified in the controller's Customer menu. If the level drops below the defined
minimum, the "WV" make-up valve opens and fills the primary tank.
Note!
To complete the make-up function from the drinking water system,
Reflex offers the Fillset with integrated system separator and Fillsoft
softening equipment,  4.6 "Optional equipment and accessories",
 30.
7.4.1.1
Using a single-tank system
1
Heat generator
2
"MAG" expansion vessel
3
Primary vessel
4
Control unit
5
Reflex Fillset
ST
Dirt trap
WC
Make-up pipe
PIS
Pressure transducer
WV
Make-up solenoid valve
EC
Degassing line
For gas-rich water from the system.
For degassed water into the system.
LIS
Level sensor
Single boiler system ≤ 350 kW, water temperature < 100 °C.
Connect the Reflex Fillset with integrated system separator upstream
when using mains water for make-up.
If you don't connect a Reflex Fillset upstream, use an "ST" dirt trap with a
mesh size ≥ 0.25 mm for the make-up.
Note!
The quality of the make-up water must comply with the applicable
standards such as VDI 2035.
If you cannot achieve this quality, use the Reflex Fillsoft to soften
the make-up water from the mains water network.
7.4.1.2
1
2
3
4
5
WC
PIS
WV
ST
EC
LIS
District heating water is particularly suitable as make-up water.
Water treatment is not necessary.
Use an "ST" dirt trap with a mesh size ≥ 0.25 mm for the make-up.
7.4.1.3
1
2
3
4
5
6
WC
PIS
WV
ST
Variomat Touch — 09.09.2022-Rev. C
Using a district heating substation
District heating house substation
Primary vessel
"MAG" expansion vessel
Site-provided make-up unit
Control unit
Make-up pipe
Pressure transducer
Make-up solenoid valve
Dirt trap
Degassing line
For gas-rich water from the system.
For degassed water into the system.
Level sensor
Note!
You require the approval of the district heating water supplier.
Use in a system with central return flow admixture
Heat generator
"MAG" expansion vessel
Primary vessel
Control unit
Reflex Fillsoft
Fillset Impuls
Make-up pipe
Pressure transducer
Make-up solenoid valve
Dirt trap