Installation
EC
Degassing line
For gas-rich water from the system.
For degassed water into the system.
LIS
Level sensor
Make-up with water via a softening system.
Always integrate the device in the "V" main volume flow to ensure
degassing the system water. It is the system side in systems with central
return flow admixture or hydraulic switching points. The vessel of the heat
generator must be fitted with an individual protective device.
When using Reflex Fillsoft softening systems, always install the Fillset
Impulse.
The device controller evaluates the make-up quantities and signals a
required replacement of the softening cartridges.
Note!
The quality of the make-up water must comply with the applicable
standards such as VDI 2035.
7.5
Electrical connection
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
Ensure that the supply cable to the device is disconnected and secured
against being switched back on.
Ensure that the system is secured and cannot be reactivated by other
persons.
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical locally
applicable electrical engineering regulations.
For the electrical connection, you must differentiate between a connection
component and an operating component.
Connection component cover
1
(hinged)
2
Main switch
3
Operating unit cover (hinged)
RS-485 interfaces
Pressure and Level
outputs
The following descriptions apply to standard systems and are limited to the
necessary user-provided connections.
1.
Disconnect the system from the power source and secure it against
unintentional reactivation.
2.
Remove the covers.
DANGER Risk of serious injury or death due to electric shock. Some
parts of the device's circuit board may still be live with 230 V even after the
device has been physically isolated from the power supply by pulling out of
the mains plug. Before you remove the covers, completely isolate the
device controller from the power supply. Verify that the main circuit board
is voltage-free.
3.
Insert a suitable screwed cable gland for the cable bushing at the rear of
the connection component. M16 or M20, for example.
38 — English
4
Touch control
5
Connection component rear
6
Cable bushings
Supply and fusing
Floating contacts
Pump connection "PU"
Variomat Touch — 09.09.2022-Rev. C
4.
Thread all cables to be connected through the cable glands.
5.
Connect all cables as shown in the terminal diagrams.
For installer supplied fusing, comply with the connected loads of the
device ,  6 "Technical data",  33.
6.
Install the cover.
7.
Connect the mains plug to the 230 V power supply.
8.
Activate the system.
The electrical connection is completed.
7.5.1
Terminal diagram
7.5.2
Terminal plan, connection component
1
Pressure
2
Level
Terminal
Signal
number
Supply
X0/1
L
X0/2
N
Supply 230 V, maximum 16 A
X0/3
PE
X0/1
L1
400 V supply,
X0/2
L2
maximum 20 A
X0/3
L3
(applies only to Variomat Giga
X0/4
N
and Variomat 140!)
X0/6
PE
Circuit board
1
PE
2
N
Voltage supply
3
L
4
Y1
5
N
Make-up solenoid valve WV
6
PE
7
Y2
PV 1 overflow valve (motor ball
8
N
valve or solenoid valve)
9
PE
10
Y3
PV 2 overflow valve (motor ball
11
N
valve or solenoid valve)
12
PE
13
Dry run protection message
(potential free)
14
Max. 230 V, 2 A
15
M1
16
N
PU 1 pump
17
PE
18
M2
19
N
PU 2 pump
20
PE
21
FB1
Pump 1 voltage monitoring
22a
FB2a
Pump 2 voltage monitoring
3
Fuses
Function
Wiring
On-site
On-site
Factory-
provided
Factory-
provided
--
---
On-site
Factory-
provided
Factory-
provided
Factory-
provided
Factory-
provided