11.3
Inspection
11.3.1
Pressure-bearing components
Comply with all applicable national regulations for the operation of pressure
equipment. De-pressurise all pressurised components prior to inspection (see
disassembly information).
11.3.2
Inspection prior to commissioning
In Germany, follow the Industrial Safety Regulation
[Betriebssicherheitsverordnung] Section 15 and Section 15 (3) in particular.
11.3.3
Inspection intervals
Recommended maximum inspection intervals for operation in Germany
pursuant to Section 16 of the Industrial Safety Regulation
[Betriebssicherheitsverordnung] and the vessel classification of the device in
diagram 2 of the Directive 2014/68/EC, applicable in strict compliance with the
Reflex Installation, Operation and Maintenance Manual.
External inspection:
No requirement according to Annex 2, Section 4, 5.8.
Internal inspection:
Maximum interval according to Annex 2, Section 4, 5 and 6; if necessary, suitable
replacement actions are to be taken (such as wall thickness measurement and
comparison with the design specification which may be requested from the
manufacturer).
Strength test:
Maximum interval according to Annex 2, Section 4, 5 and 6.
Furthermore, compliance with Section 16 of the Industrial Safety Regulation and
Section 16 (1) in particular, in conjunction with Annex 2, Section 4, 6.6 and
Annex 2, Section 4, 5.8, must be ensured.
The actual intervals must be specified by the operating company based on a
safety evaluation taking into consideration the actual operating conditions,
experience with the mode of operation and charging material and the applicable
national regulations for the operation of pressure equipment.
12
Disassembly
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the supply cable to the device is disconnected and secured
against being switched back on.
•
Ensure that the system is secured and cannot be reactivated by other
persons.
•
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical locally
applicable electrical engineering regulations.
CAUTION
Risk of burns
Escaping hot medium can cause burns.
•
Maintain a sufficient distance from the escaping medium.
•
Wear suitable personal protective equipment (safety gloves and
goggles).
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wait until hot surfaces have cooled down or wear protective safety
gloves.
•
The operating authority is required to place appropriate warning signs
in the vicinity of the device.
inhalt_en
Risk of injury due to pressurised liquid
If installation or maintenance work is not carried out correctly, there is a risk
of burns and other injuries at the connection points, if pressurised hot water
or steam suddenly escapes.
•
•
•
Prior to dismantling, block off all "water"-side connections to the device.
•
De-pressurise the device by venting it.
1.
Disconnect the system from the power supply and secure it against
unintended reactivation.
2.
Disconnect the power cable of the device from the power supply.
3.
Disconnect and remove all cables from the terminals of the device
controller.
parts of the device's circuit board may still be live with 230 V even after the
device has been physically isolated from the power supply by pulling out of
the mains plug. Before you remove the covers, completely isolate the
device controller from the power supply. Verify that the main circuit board
is voltage-free.
4.
Disconnect the secondary tank (if provided) on the water side from the
system and the primary tank.
5.
Open the "FD" feed and drain cocks at the tanks until they are completely
empty and de-pressurised.
6.
Undo all hose and pipe connections to the vessels and the control unit of
the device to the system and remove them completely.
7.
If necessary, remove the tanks and the control unit from the system area.
13
13.1
Central customer service
Central telephone number: +49 (0)2382 7069 - 0
Customer Service extension: +49 (0)2382 7069 - 9505
Fax: +49 (0)2382 7069 - 9523
E-mail: service@reflex.de
Technical Hotline
For questions about our products
Telephone number: +49 (0)2382 7069-9546
Monday to Friday 8:00 to 16:30
13.2
Device conformity declarations are available on the Reflex homepage.
www.reflex-winkelmann.com/konformitaetserklaerungen
Alternatively, scan the QR code:
13.3
The respective statutory guarantee regulations apply.
Variomat Touch — 09.09.2022-Rev. C
CAUTION
Ensure proper disassembly.
Ensure that the system is de-pressurised before performing the
disassembly.
DANGER – Risk of serious injury or death due to electric shock. Some
Note!
When using environmentally harmful media, an adequate liquid
capture facility must be provided. Moreover, the operator is
obliged to ensure correct disposal of any such media.
Annex
Reflex Customer Service
Conformity and standards
Guarantee
Disassembly
English — 49