Terminal
Signal
number
22b
FB2b
---
23
NC
Group message (potential free)
24
COM
Max. 230 V, 2 A
25
NO
27
M1
Flat plug for supply, pump 1
31
M2
Flat plug for supply, pump 2
35
+18 V (blue)
Analogue input, LIS level
36
GND
measurement
37
AE (brown)
at the primary vessel
38
PE (shield)
39
+18 V (blue)
Analogue input, "PIS" pressure
40
GND
measuring
41
AE (brown)
at the primary vessel
42
PE (shield)
43
+24 V
Digital inputs
44
E1
E1: Contact water meter
45
E2
E2: Low water switch
51
GND
52
+24 V (supply)
0 – 10 V
53
PV 2 overflow valve (motor ball
(correcting
valve), only in VS 2-2
variable)
0 – 10 V
54
(feedback)
55
GND
56
+24 V (supply)
57
0 – 10 V
PV 1 overflow valve (motor ball
(correcting
valve)
variable)
58
0 – 10 V
(feedback)
7.5.3
Terminal plan, operating unit
1
RS-485 interface
2
RS-485 interface
3
I/O interface
4
Micro-SD card
5
10 V supply
Terminal
Signal
number
1
A
RS-485 interface
2
B
S1 networking
3
GND S1
Function
Wiring
---
On-site
Factory-
provided
Factory-
provided
Cable:
factory-
provided;
Sensor plug:
on-site
On-site,
optional
On-site,
optional
Factory-
provided
---
Factory-
provided
Factory-
provided
6
Analogue outputs for Pressure
and Level
7
Battery compartment
8
Anybus module slot
9
DIP switch 2
10 DIP switch 1
Function
Wiring
On-site
Variomat Touch — 09.09.2022-Rev. C
Terminal
Signal
number
4
A
RS-485 interface
5
B
S2 modules: Expansion or
communication module
6
GND S2
7
+5 V
8
R × D
I/O interface: Interface to the
main board
9
T × D
10
GND IO1
11
---
12
---
---
13
---
14
---
15
10 V~
16
10 V supply
17
FE
18
Y2PE
(shielding)
Analogue outputs: Pressure and
19
Pressure
Level
20
GNDA
Standard 4 – 20 mA
21
Level
22
GNDA
7.5.4
RS-485 interface
Use the S1 and S2 RS-485 interfaces to retrieve all controller data and to enable
the communication with control centres or other devices.
•
S1 interface
–
A maximum 10 devices can be used in a master-slave linked circuit
via the this interface.
•
S2 interface
–
"PIS" pressure and "LIS" level.
–
Operating modes of the "PU" pumps.
–
Operating states of the motorised ball valve/solenoid valve.
–
Values of the "FQIRA +" contact water meter.
–
All messages.
–
All entries in the fault memory.
The following bus modules form part of the optional accessories available for
interface communication.
Note!
If required, please contact the Reflex Customer Service for the protocol
of the RS-485 interface, details of the connections and information about
the accessories offered.
7.5.4.1
Connecting the RS-485 interface
Main board of the Control Touch controller.
No
Component
.
1
Connection terminals for RS-485 connection
2
Dip switch 1
Proceed as follows:
1.
Use a screened cable to connect the RS-485 interface to the main board.
•
S 1
–
Terminal 1 (A+)
–
Terminal 2(B-)
–
Terminal 3(GND)
Installation
Function
Wiring
On-site
Factory
---
Factory
On-site
English — 39