11.9.
SETTING THE PROTECTED PARAMETER "HEATING SETPOINT"
This parameter allows you to set the maximum temperature above which disable any resistance or accessory battery to water,
which may be contained in the plenum or accessories PLS PLSM (if the plenum or PLS PLSM not provide, this parameter will be
considered);
To set the heating setpoint it is necessary to enter in the password protected menu (as shown in paragraph 11.7), using the navi-
gation keys to run through the operating parameters until the parameter SPH is displayed. Press the MODE/SELECT key to enter
the parameter modification mode and use the navigation keys to select the desired value (the accepted range of values is
from 12°C to 40°C, default value is 20°C). Then press the MODE/SELECT key to confirm the selection and exit from the parameter
modification mode.
Note: To enable the electrical resistance must set the AUX mode (see parameter 11.3). The water coil aftertreatment winter, if
present, is automatically activated in manual mode, AUX or AUTO, depending on the need.
Season parameter (SPH):
1
2
The appearance of the SET icon shows that the system is
awaiting modification of the parameter (default heating set-
point value 20°C)
3
Once the value is confirmed the name of the parameter
is again displayed.
WARNING: Once in the password protected menu press-
ing the navigation keys (
the various parameters. If during the display of the SEA
parameter the (
menu and to return to the password menu it is necessary
to repeat the procedure detailed in paragraph 11.7.
,
) permits moving between
) key is pressed this exits the password
1
Activate parameter modi-
fication mode
2
Set the desired heating
setpoint
3
Confirm the selected
value
4238010_02 - 1302