1.2
Intended use
The DT-Mobil PRO Hybrid mobile diesel filling
station is an approved IBC (Intermediate Bulk
Container) in accordance with the ADR for
hazardous goods in packaging group II + III (liquid,
water-polluting substances).
The filling station is intended for use in different
places in the open air.
It may only be filled or transported with valid
inspection/testing. Repeat test two and a half years
after date of manufacture in accordance with ADR
6.5.4.4.1 b) and 6.5.4.4.2.
Repeat test five years after date of manufacture in
accordance with ADR 6.5.4.4.1 a) and 6.5.4.4.2.
Please note that the transport approval for all
combination IBCs with a plastic inner tank for
diesel is limited to 5 years. After this period,
the inner tank for diesel must be replaced. We
offer you this tank replacement service incl. test
certificate in accordance with the ADR.
Regarding the DT-Mobil PRO Hybrid
approval D/BAM 15151 with 8 years validity, see
also "Availability of use". (section 12.2.1)
Please note: The tests are to be repeated at 5-year
intervals.
In addition, the steel collection container meets
the requirements for collection trays under StawaR
[guidelines for steel trays] in terms of design,
materials, and manufacturing, welding and testing
methods. The regulations for fire prevention and
operational safety must be observed.
Operating temperature range: -10°C to +40°C
i
Important!
Only clean media may be used.
Correct usage (preferably) involves the
following liquids:
Diesel fuel
Fuel oil
Biodiesel
46
For the facilitated transport of dangerous goods
(<1000 points) the following is required according
to the ADR:
labelling (stickers) on the filling station
mandatory equipment with fire extinguisher
(2 kg)
carrying an accompanying document (here,
transport document – observe national
exceptions) (no transport document in Germany
– exception 18 S)
observation of the "1000 point rule" according
to table 1.1.3.6 ADR, i.e. total quantity of the
transport unit < 1000 points
» Diesel fuel 1 l = 1 point
Repeat inspection 2½ years after date of
manufacture by skilled and trained person
required. The ADR approval expires after 5 years.
i
ADR
8
Important!
Be sure to read the relevant provisions of
the ADR.

Publicidad

loading