Table 2.3
Model
PIPE
ΦD0(OD)
Gas pipe
25.4
252-335
(8-12HP)
Liquid pipe
12.7
Gas pipe
28.6
400-450
Liquid pipe
(14-16HP)
15.9
Gas pipe
31.8
500-670
(18-24HP)
Liquid pipe
19.1
Gas pipe
31.8
730
(26HP)
Liquid pipe
22.2
Gas pipe
38.1
785-900
(28-32HP)
Liquid pipe
22.2
L-shaped pipe size
ΦD1
ΦD0
2.4 Pipe Fittings
The schematic after the L-shaped pipe (from
accessories) is properly connected to the unit is
shown below:
Liquid pipe
Gas pipe
Check port (used to measure
connection
connection
system pressure, charge
port
port
refrigerant and vacuumize)
65
41
207
73
Table 2.4
HP
8-12
14-16
18-24
SIZE
ΦA(ID)
Φ12.7
Φ15.9
Φ19.1
ΦB(ID)
Φ25.4
Φ28.6
Φ31.8
3 OUTDOOR UNIT COMBINATION
3.1 Overview
This chapter contains the following information:
List of branch joint fittings.
Recommended combination for outdoor units.
L2
L1
130
230
160
265
125
225
155
255
130
220
162
245
130
130
165
165
155
115
165
165
L4
L2
Figure 2.4
ΦA
ΦB
Figure 2.5
Unit: mm
26
28-32
Φ22.2
Φ22.2
Φ31.8
Φ38.1
14
ΦD1(ID)
L3
L4
20
20
25.4
15
15
12.7
20
20
28.6
15
15
15.9
25
20
28.6
15
15
15.9
25
25
31.8
20
20
22.2
20
20
34.9
20
20
22.2
3.2 Branch Joints
Table 3.1 For JR8(V) combinable series
Description
Outdoor Unit Branch
Joint Assembly
Indoor Unit Branch
Joint Assembly
On the choice of branch joints, refer to section "4.3.3
Selecting piping diameters".
3.3 Recommended Outdoor Unit
Combination
CAUTION
The total capacity of the IDU shall be
between
50%–130%
capacity of the ODU.
In the system where all indoor units are
running at the same time, the total capacity of
the indoor units should be less than or equal
to the combined capacity of the outdoor unit
to prevent overloading in poor operating
conditions or narrow operating space.
The total capacity of the indoor units can be
up to a maximum of 130% of the combined
capacity of the outdoor unit for a system
where not all the indoor units are operating at
the same time.
If the system is being used in a cold region
(ambient temperature is -10°C or below) or a
very hot, heavy-load environment, the total
capacity of the indoor units should be less
than the combined capacity of the outdoor
unit.
The heating capacity of the heat pump will
reduce
when
the
temperature is lowered. Therefore, when
installing a heat pump in an area with low
temperatures, it is recommended to use the
IDU with an auxiliary heater.
Unit: mm
ΦD2(ID)
R
50
25.4
25
12.7
55
28.6
30
15.9
60
31.8
40
19.1
60
31.8
40
22.2
80
38.1
40
22.2
Model
EVRO-BP2
EVRO-BP2G
EVRO-BP3
EVRO-BP3G
EVRI-BP1
EVRI-BP2
EVRI-BP3
EVRI-BP4
EVRI-BP5
EVRI-BP6
EVRI-BP7
of
the
combined
outdoor
ambient