Electric wiring and the application
The outdoor and all indoor units are in parallel through 2 non-polar wires.
Three wiring methods between wired controller and indoor unit:
indoor 2 is wired control master unit, the others are wired control slave units. Wired controller and the master indoor
(directly connected to wired controller) is connected by 3 polar wires; the other indoors and the master indoors are
connected by 2 polar wires.
controller are connected by 3 polar wires.
set as master wired controller, and the other is slave wired controller. Master/slave wired controller, and master/indoor
are connected by 3 polar wires.
When indoor is controlled by remote controller, refer to the "wired control master unit/wired control slave unit/remote
control unit table".A, B, C on signal terminal block need not wires and not connect the wired controller.
outdoor
VVFA-150R-01T32
power source: 3N~, 380-415V, 50/60Hz
indoor 1
(wall mounted unit)
power source: 1PH, 220-240V~, 50/60Hz
Indoor and outdoor use their individual power source. All indoors use one power source. Must install the leakage breaker
and the over current breaker, or electric shock will occur.
Outdoor power source and power cable
Item
Model
VVFA-125R-01M22
VVFA-150R-01M22
VVFA-150R-01T32
•
• To avide electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical
parts.Even after 1 minute,always measure the voltage at the terminals of main circuit capacitors or electrical parts and
before touching, make sure that those voltages are 50VDC or less.
• To persons in charge of electrical wiring work: Do not oerate the unit until the refrigerant piping is complete. (Running
it before the piping is ready will break the compressor)
• Each outdoor must be earthed well.
outdoor
VVFA-125R-01M22
VVFA-150R-01M22
power source: 1PH, 220-240V~, 50/60Hz
indoor 2
(wall mounted unit)
power source: 1PH, 220-240V~, 50/60Hz
Power cable
Power
section
source
2
(mm
10
1PH, 220-240V~,
50/60Hz
10
3N~, 380-415V,
4
50/60Hz
Rated current of residual
Circuit
circuit breaker (A)
breaker
Ground fault interruptor (mA)
)
(A)
response time (S)
50
50A 30mA below 0.1S
50
50A 30mA below 0.1S
20
20A 30mA below 0.1S
14
indoor 3
(non wall mounted unit)
power source: 1PH, 220-240V~, 50/60Hz
Ground wire
Section
Screw
2
(mm
)
10
10
4
M5
M5
M5