13. Depending on the grid configuration, connect the
neutral conductor to connecting terminal plate N
(see Section 6.3.1 "Requirements for the AC
Connection", page 28).
14. Connect the conductors L1, L2 and L3 to the
terminals L1, L2 and L3 according to the label.
Ensure that the assignment is correct.
15.
Danger of crushing when locking levers snap shut
The locking levers close by snapping down fast and hard.
• Press the locking levers of the terminal block for the AC cable down with your thumb
only. Do not grip the entire terminal block for the AC cable between finger and thumb
and keep fingers out from under the locking levers.
16. Ensure that the correct conductors are assigned to all the terminals.
17. Ensure that all locking levers of the connecting terminal plate are closed and all conductors
are tightly connected.
6.3.3

Connecting Additional Grounding

The inverter is equipped with a grounding terminal with two connection points on the DC side for
additional grounding (e.g. use of a grounding electrode).
The grounding terminal is yellow/green and identified as follows:
• Equipment grounding terminal: symbol
• Grounding electrode conductor: labeling GEC

Cable requirements:

☐ The cable must be designed in accordance with the local installation requirements and for
temperatures of over +90°C (+194°F).
☐ Cable type: copper wire
☐ Conductor cross-section: 10 mm² to 35 mm² (8 AWG to 2 AWG)
Installation Manual
CAUTION
STPTL-US-10-IA-xx-20
6 Electrical Connection
31