Principle wiring for NCNC or NCNO control
When using the NCNC or NCNO control, the safety switches are supplied by the clock signal (S21,
S11). Safety input 1 (S12) is connected with S11 via the switch. Safety input 2 (S22) is connected
with S21 via the switch. Cross-circuits on the safety inputs are monitored by the AS3-SV safety
valve in this control. Start (pressurization) takes place using the start input X2 in this control.
For principle wiring for NCNC control, see
For principle wiring for NCNO control, see
Principle wiring for PM control
Input M of the AS3-SV safety valve must be connected with the safe negative output D0-M
(e.g. safe output assembly) of a PLC. Input P of the AS3-SV safety valve must be connected with
the safe positive output D0-P (e.g. safe output assembly) of a PLC. The "automatic start" function
is used in this operating mode, therefore X2 must be connected with 24 V DC. The contacts have
the following assignment for PM control:
X2D
Pin
Function
1
nc, not connected (not connect)
nc
1
nc
2
nc, not connected (not connect)
2
M
3
M-input (safety input 2)
3
P
4
4
P-input (safety input 1)
nc
5
5
nc, not connected (not connect)
For principle wiring for PM control, see
Connect ground (FE, function potential compensation)
A ground connection is available on the device. To discharge EMC interferences, connect the
FE connection (
–9) to the AS3-SV safety valve via a low-impedance line to functional earth.
2
The line cross-section must be selected according to the application and implemented according
to DIN EN 60204-1/IEC 60204-1.
7
Commissioning
Danger of injury while working on the system!
Working while the system is running can cause major injuries from moving machinery.
O
Maintain a sufficient safety distance to moving machine components.
O
Do not work on the system while it is running.

Checking the connections

O
Make sure that all plugs are correctly connected before commissioning.
Take the AS3-SV safety valve into operation
Proceed as follows in order to take the AS3-SV safety valve into operation:
1. Switch on the pneumatic supply.
2. Switch on the 24 V DC supply voltage.
"Pressurization" function
If the AS3-SV safety valve should pressurize the machines, you must switch both safety inputs 1
and 2 with the right signal sequence. If the signal sequence is not correct, the AS3-SV safety
valve goes into the safe state. Exhausting of the operating line is the safe state.
"Exhaust" function
If the AS3-SV safety valve should exhaust the machines, you must switch both safety inputs 1
and 2 with the right signal sequence. The AS3-SV safety valve goes into the safe state if the
AS3-SV safety valve is isolated from the supply voltage or if a fault occurs during operation.
Exhausting of the operating line is the safe state.
Signal sequence when switching on
The following signal sequence results when switching on the AS3-SV safety valve (see
The AS3-SV safety valve is not supplied with 24 V DC before time 1. Signal output (41, 42) is open
(41, 42=0) and the RUN-LED is off (0). The AS3-SV safety valve exhausts the operating line.
The AS3-SV safety valve is supplied with 24 V DC at time 1. The RUN LED and all other LEDs flash
briefly when switched on. The device performs a self-test. This self-test takes a maximum of
1.5 s. After the self-test (4) has been successfully carried out, the AS3-SV safety valve is in the
ready state (2). The RUN-LED (1) is illuminated in the ready state and the signal output is closed
(41, 42=1). The AS3-SV safety valve is ready for control via both safety inputs.
If the device is disconnected from the supply voltage at time 4,
W
the AS3-SV safety valve exhausts,
W
the RUN LED is not illuminated and
W
the signal output is open (41, 42=0).
Signal sequence for PP control
The following signal sequence results during PP control of the AS3-SV safety valve (see
The AS3-SV safety valve is in the ready state before time 1, but is not activated. In this state
(AS3-SV=0) the AS3-SV safety valve exhausts the operating line.
Signal input S22 is actuated with 24 V at time 1. If signal input S12 is also actuated with 24 V
within synchronization time (4), the AS3-SV safety valve goes into the pressurized state
(AS3-SOV=1) at time 2. OUT LED illuminates and indicates the activated state.
The synchronization time for monitoring (4) is 0.5 s. The state of signal inputs 1 and 2 is
displayed by the IN 1 LED and IN 2 LED.
.
8
9
.
.
10
WARNING
If the interval between signal inputs 1 and 2 is longer than the synchronization time for
monitoring, the AS3-SV safety valve remains in the non-activated state. In this state (AS3-SV=0)
the AS3-SV safety valve exhausts the operating line and OUT LED is not illuminated. The IN 1 LED
and IN 2 LED flash fast and indicate that signal inputs 1 and 2 have not been actuated
synchronously.
If signal input 1 and/or signal input 2 is actuated with 0 at time 3, the AS3-SV safety valve goes
into the non-activated state (AS3-SOV=0) and exhausts the operating line. OUT LED is off. Signal
inputs 1 and 2 must be on 0 to re-pressurize. The IN 1 and IN 2 LEDs are off in this state.
Signal sequence for NCNC control
The following signal sequence results during NCNC control of the AS3-SV safety valve (see
The AS3-SV safety valve is in the ready state before time 1, but is not activated. In this state
(AS3-SV=0) the AS3-SV safety valve exhausts the operating line.
Signal input S22 is connected with clock output S21 at time 1 via the switch. If signal input S12
is connected with clock output S11 via the second switch within synchronization time (6), the
AS3-SV safety valve goes into the "wait for start" state at time 2. The AS3-SV safety valve
remains in the non-activated state (AS3-SOV=0) and the exhausts the operating line. OUT LED
indicates this state by flashing slow.
The synchronization time for monitoring the signal inputs is 0.5 s. The state of signal inputs 1
and 2 is displayed by the IN 1 LED and IN 2 LED.
If the interval between signal inputs 1 and 2 is longer than the synchronization time for
monitoring, the AS3-SV safety valve remains in the non-activated state. In this state (AS3-SV=0)
the AS3-SV safety valve exhausts the operating line and OUT LED is not illuminated. The IN 1 LED
and IN 2 LED flash fast and indicate that signal inputs 1 and 2 have not been actuated
synchronously.
If start signal X2 is changed from 0 V to 24 V (positive flank) at time 3 and is changed back from
24 V to 0 V (negative flank) at time 4, the AS3-SV safety goes into the pressurized state
(AS3-SV=1) at time 4. OUT LED illuminates and indicates the activated state. The time for
monitoring signal X2 is between a minimum of 0.03 s and maximum 3 s. If X2 is not actuated
within this monitoring time, the AS3-SV safety valve remains in the exhausted state (AS3-SV=0).
If the connection between S11 and S12 or between S21 and S22 is interrupted via the
corresponding switch after time 4, the AS3-SV safety valve goes into the non-activated state
(AS3-SOV=0) and exhausts the operating line at time 5. OUT LED is off. Both signal inputs 1 and
2 must be open/interrupted to re-pressurize. The IN 1 and IN 2 LEDs are off in this state.
Signal sequence for NCNO control
The following signal sequence results during NCNO control of the AS3-SV safety valve (see
The AS3-SV safety valve is in the ready state before time 1, but is not activated. In this state
(AS3-SV=0) the AS3-SV safety valve exhausts the operating line.
The switch opens the connection between signal input S22 and clock output S21 at time 1. If
signal input S12 is connected with clock output S11 via the second switch within synchronization
time (6), the AS3-SV safety valve goes into the "wait for start" state at time 2. The AS3-SV safety
valve remains in the non-activated state (AS3-SV=0) and the exhausts the operating line. OUT
LED indicates this state by flashing slow.
The synchronization time for monitoring the signal inputs is 0.5 s. The state of signal inputs 1
and 2 is displayed by the IN 1 LED and IN 2 LED.
If the interval between signal inputs 1 and 2 is longer than the synchronization time for
monitoring, the AS3-SV safety valve remains in the non-activated state. In this state (AS3-SV=0)
the AS3-SV safety valve exhausts the operating line and OUT LED is not illuminated. The IN 1 LED
and IN 2 LED flash fast and indicate that signal inputs 1 and 2 have not been actuated
synchronously.
If start signal X2 is changed from 0 V to 24 V (positive flank) at time 3 and is changed back from
24 V to 0 V (negative flank) at time 4, the AS3-SV safety goes into the pressurized state
(AS3-SV=1) at time 4. OUT LED illuminates and indicates the activated state. The time for
monitoring signal X2 is between a minimum of 0.03 s and maximum 3 s. If X2 is not actuated
within this monitoring time, the AS3-SV safety valve remains in the exhausted state (AS3-SV=0).
If the connection between S11 and S12 is opened via the corresponding switch after time 4 or
the connection between S21 and S22 is closed by the corresponding switch, the AS3-SV safety
valve goes into the non-activated state (AS3-SOV=0) and exhausts the operating line at time 5.
OUT LED is off. Both signal inputs 1 and 2 must be open/closed to re-pressurize. LED IN 1 and
IN 2 are off in this state.
Signal sequence for PM control
The following signal sequence results during PM control of the AS3-SV safety valve (see
The AS3-SV safety valve is in the ready state but is not activated before time 1. In this state
11
).
(AS3-SV=0) the AS3-SV safety valve exhausts the operating line.
Signal input M is actuated with 0 V at time 1. If signal input P is also actuated with 24 V within
synchronization time (4), the AS3-SV safety valve goes into the pressurized state (AS3-SV=1) at
time 2. OUT LED illuminates and indicates the activated state.
The synchronization time for monitoring (4) is 0.5 s. The state of signal inputs P and M is
displayed by the IN 1 LED and IN 2 LED.
If the interval between signal inputs P and M is longer than the synchronization time for
monitoring, the AS3-SV safety valve remains in the non-activated state. In this state (AS3-SV=0)
the AS3-SV safety valve exhausts the operating line and OUT LED is not illuminated. The IN 1 LED
and IN 2 LED flash fast and indicate that signal inputs 1 and 2 have not been actuated
synchronously.
If signal input P is not actuated with 24 V or if signal input M is not actuated with 0 at time 3, the
AS3-SV safety valve goes into the non-activated state (AS3-SV=0) and exhausts the operating
line. OUT LED is off.
The signal input must be at 0 V and signal input M not at 0 V to re-pressurize. The IN 1 and IN 2
).
12
LEDs are off in this state.
Signal sequence when a fault occurs
The AS3-SV safety valve does into the safe state if a fault occurs during operation of the AS3-SV
safety valve. Exhausting of the operating line is the safe state. If an error occurs:
W
The AS3-SV safety valve exhausts the operating line,
W
opens the signal output and
W
the red LED shows a flash code for the fault.