Ecoflam MAX GAS 350 LN PR-MD TC SGT 230-50 BT330 Manual De Uso página 13

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 36
Air pressure switch calibration
The air pressure switch is provided for
monitoring the pressure of the
combustion air fan.
Unscrew screws A and B and remove
cover C.
After the air and gas setting you have to
calibrate the air switch with the burner
working on the low flame by slowly turning
the relative knob clockwise until the burner
locks out. Read the value and then
decrease it by 15%.
Min gas pressure switch
The gas pressure switch has the function
to check that the gas pressure before the
gas valve does have the minimum
pressure to make the burner running
correctly.
Unscrew off and remove cover M.
- Set knob N to a value equal to 60% of
gas nominal feed pressure (i.e. for natural
420010537501
WARNING: the air pressure switch shall
prevent the air pressure to go below 85%
from the adjustment value in order to
prevent the CO in the fumes to exceed 1%
(10000 ppm).
gas nom. pressure = 20 mbar, set knob to
a value of 12 mbar; for LPG nom. pressure
of G30/G31- 30/37 mbar, set knob to a
value of 18 mbar). Screw up cover M.
C
A
B
M
I
L
www.ecoflam-burners.com
EN
D
N
13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max gas 350 ln pr-md tl sgt 230-50 bt330Max gas 500 ln pr-md tc sgt 400-50 bt330Max gas 500 ln pr-md tl sgt 400-50 bt330314340131434023143406 ... Mostrar todo

Tabla de contenido