4 - TROUBLESHOOTING

Faults are indicated on the CDC-VMA console by a code from
0 to 8.
With the PEGASE VMA 10 software the faults are indicated
clearly in the fault window.
The table below can be used to analyse faults and specifies
any checks which should be performed.
Fault code on
Indication of fault on
CDC-VMA
PEGASE
0
NO FAULT
MOTOR
1
OVERHEATING
Red LED illuminated
OVERVOLTAGE
2
Red LED flashing
OVERCURRENT
3
Red LED illuminated
LOCKED ROTOR
4
Red LED illuminated
BUS UNDERVOLTAGE
5
Red LED flashing
EEPROM
6
Red LED illuminated
SERIAL LINK
7
Red LED illuminated
MODULE FAULT
8
Red LED illuminated
FAULTS CAN ONLY BE CLEARED BY SWITCHING OFF THE VARMECA 10.
Fault specific to the use of the CDC-VMA
console
Fault specific to the use of the software
PEGASE VMA 10
46
PARAMETER-SETTING MANUAL
VARMECA 10
Variable speed motors and geared motors
TROUBLESHOOTING
- check if the motor is overloaded
(orange LED illuminated)
- check the set rating and the motor power
- make sure that the boost adjustment (P11) has not been modified
- check the mains supply voltage
- check that the deceleration ramp is long enough for applications with high inertia
- check that there is no short circuit occurring from a motor winding or on the
connections
- check the motor insulation
- check that the deceleration ramp is long enough for applications with high inertia
- check the set rating and the motor power
- internal product fault
- check if the motor is overloaded or has stalled (green LED flashing)
- check the mains supply voltage
- make sure that the VARMECA 10 is not affected by interference
- internal product fault
- communication fault between the EEPROM and the controller - product fault
- very sudden overcurrent (possible causes: see OVERCURRENT fault)
- IGBT power module overheating. Check that the unit is not operating at an
ambient temperature which is too high
- IGBT power module fault. Internal product fault
- Check the connection cable.
- Check that the VARMECA 10 is correctly supplied.
- Check the connection cable.
- Check that the VARMECA 10 is correctly supplied.
- Check that the serial port is correctly configured.
Checks to make, possible causes
overheating fault I
CONSOLE LINK FAULT
COMMUNICATION PROBLEM WITH THE VARMECA 10