2.5 - The VARMECA 10 parameters

List and description of the parameters which can be accessed by the CDC-VMA console
Display
P01 F min
minimum operating frequency
calibration of the min. reference
P02 REF 0 V - 4 mA
0 V or 4 mA
maximum operating frequency
P03 F max
(according to mini DIP K2 position)
P04 REF 10 V - 20 mA
calibration of the max. reference
acceleration ramp
P05 ACCEL.
ramp value to pass from 0 to 50 Hz
deceleration ramp
P06 DECEL.
ramp value to pass from 50 to 0 Hz
stop mode
P07 STOP MODE
P08 UN MOT
voltage applied to the motor from the base frequency
(1)
(percentage of mains voltage: base 400 V)
P09 FN MOT
motor base frequency
(1)
selection of voltage/frequency ratio
0 = fixed U / F
P10 U / F
the P08 voltage will be applied at the P08 frequency point
(1)
1 = dynamic U / F
the voltage adapts automatically to the motor load
P11 BOOST
value of voltage applied in low frequencies
(1)
(percentage of mains voltage)
P12 OVER BOOST
value of voltage during starting phase
(1)
(percentage of mains voltage)
switching frequency
P13 F PWM
terminal block configuration
P14 CONFIG
P15 VP1-1
preset speed 1 in options 1 and 4
preset speed 2 in options 1 and 4 or preset speed 1 in
P16 VP2-1 VP1-2
option 2
P17 VP2-2
preset speed 2 in option 2
P18 VP3-2
preset speed 3 in option 2
PARAMETER-SETTING MANUAL
VARMECA 10
COMMISSIONING THE CDC-VMA CONSOLE
Description
0 = freewheel stop
1 = stop according to ramp
0 = 4 kHz
1 = 6 kHz
2 = 8 kHz
3 = 11 kHz
0 = standard
1 = option 1 - 2 preset speeds and 2 operating
directions
2 = option 2 - analogue reference and 3 preset
speeds - 1 operating direction
3 = option 3 - correction of an external reference
with the local button - 2 operating directions
4 = option 4 - 2 preset speeds proportional to the
reference - 1 operating direction
(1) : the voltage/frequency ratio is illustrated at the end of the table
Ref. 3264 - 4.33/b -1.00
Adjustment range in
Factory setting
increments of 1
6 to 30 Hz
0 to 30 Hz
32 to 220 Hz
50 or 80 Hz
32 to 220 Hz
50 or 80 Hz
0 to 20 s
0 to 20 s
0 or 1
0 to 100 %
50 to 150 Hz
from 0.25 to 1.1 kW
0 or 1
from 1.5 to 7.5 kW
adapted to the
0 to 40 %
motor according to
the power
adapted to the
0 to 100 %
motor according to
the power
from 0.25 to 2.2 kW
0 to 3
from 3 to 4kW
0 to 4
6 to 220 Hz
6 to 220 Hz
6 to 220 Hz
6 to 220 Hz
12 Hz
12 Hz
3 s
3 s
1
100 %
50 Hz
0
1
3
2
0
50 Hz
60 Hz
40 Hz
70 Hz
39