Data Storage; Access Locks (Device Access Locks); Profiles And Functions (Profilecharacteristic); Process Data Structure (Pd Input Descriptor) - Balluff BMF 203K-H- C-A-PU Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 109
BMF 203K-H- _ _ -C-A _ -... / BMF 235K-H- _ _ -C-A _ -...
Magnetic Field Sensors
7
IO-Link (continued)
7.5.3

Data storage

Index
Subindex Name
Data Storage
1
0x0003 (3)
2
3
4
5
Tab. 7-6:
Data storage parameter
7.5.4

Access locks (Device Access Locks)

With the standard parameter Device Access Locks (Index
0x000C (12)) it is possible to activate or deactivate certain
functions of the IO-Link device.
With the BMF, there is the option to lock the function of the
parameter manager and the button. To do so, the
respective bit of the 2-byte value must be set to 1 (locked).
In order to unlock the function again, the bit is set to 0.
Bit 0
Lock parameter access
(not supported)
Bit 1
Lock parameter management
(supported)
Bit 2
Locking the button
(supported)
Bit 3
Lock local user interface
(not supported)
Bit 4 to 15
Reserved
Tab. 7-7:
Locking parameter data
7.5.5

Profiles and functions (ProfileCharacteristic)

The ProfileCharacteristic (Index 0x000D (13)) parameter
indicates which profile of the IO-Link device is supported.
Subindex 1 (DeviceProfileID):
0×0001 (Smart Sensor Profile)
Subindex 2 (FunctionClassID):
0×8000 (Identification Function Class)
Subindex 3 (FunctionClassID):
0×8001 (BDC Function Class)
Subindex 4 (FunctionClassID):
0×8003 (Diagnosis Function Class)
Subindex 5 (FunctionClassID):
0×8004 (teach channel)
20
english
Size
Command
1 byte
State Property
1 byte
Size
4 bytes
Parameter Checksum
4 bytes
Index List
32 bytes
Access
Values
Read/Write
The Data Storage parameter is needed
Read Only
by the IO-Link master for the data storage
Read Only
function. This parameter cannot be user
Read Only
modified.
Read Only
7.5.6

Process data structure (PD Input Descriptor)

The PD Input Descriptor parameter describes the
composition of the process data used.
Every part of the process data is described by 3 bytes.
Subindex Values
0x01
Set of Boolean (BDC 1...8)
1
0x08
0x00
0x01
2
0x01
0x08
0x01
3
0x01
0x09
Tab. 7-8:
Process data structure
Using subindex 0, the complete process data description
can be read out (see Section Process data on page 15).
Description
8-bit length
0-bit offset
Boolean (Stability)
1-bit length
8-bit offset
Boolean (Teach-In)
1-bit length
9-bit offset