Control And Command Equipment Lme 22 - baltur TBG 120 P Manual De Instrucciones De Uso

Quemadores de gas de dos etapas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CONTROL AND COMMAND EQUIPMENT LME 22...

operation, indications, diagnostics
RED
YELLOW
EK
GREEN
Both «LED» and «EK...» are positioned under the transparent button. Pressing this button you unlock the command and control device.
Possibility of two diagnostics functions:
1. Visual indication directly on the unlocking button: operation and diagnostics of device status.
2. Diagnostics with interface: in this case the OCI400 connecting cable is necessary and it can be connected to a PC with ACS400
software, or to gas analysers of different manufacturers (see technical sheet 7614).
Visual indication:
During operation the command and control device phase is indicated on the unlocking button. The following table lists all colour sequences
and their meaning. To activate the diagnostics function hold the unlocking button down for at least 3 seconds. A quick red flashing light
indicates that the function is active (see data sheet 7614). Likewise, hold the unlocking button down for at least 3 seconds to deactivate
the function (the switching will be indicated with a flashing yellow light).
Operating position
Colour code table
Condition
TW standby conditions, other intermediate statuses
Ignition phase
Correct operation, current strength of flame detector above
the minimum allowed
Incorrect operation, current strength of flame detector below
the minimum allowed
Decrease in power supply voltage
Burner in lock condition
Fault indication (see colour legend)
Extraneous light upon burner ignition
Quick flashing for diagnostics
No light
malfunction and lock cause diagnostics
In the event of a burner lock-out, the red light on the unlocking button will light up fixed.
Holding the unlocking button down for more than 3 seconds, the diagnostics phase will be activated (quick flashing red light). The table
below lists the meaning of the malfunction and lock-out cause depending on the number of flashing (always red-coloured).
Holding the unlocking button down for at least 3 seconds, the diagnostics function will be interrupted (for further details see the technical
sheet 7614).
The diagram below indicates the operations that are necessary to activate the diagnostics functions.
The unlocking button «EK...» is the main element to access all diagnostics functions
(activation and deactivation), and serves to unlock the command and control device.
The multicoloured «LED» indicates the command and control device status during both
operation and diagnostics function.
Diagnostics
Command and control device status indication
Red
Yellow
0006081522_201306
Operating position
PC interface/diagnostics
analyser
Colour sequence
. . . . . . . . . . . . . . . .
Green
12 / 20
Colours
No light
Intermittent yellow
Green
Intermittent green
Alternating Yellow and Red
Red
Intermittent red
Alternating Green and Red
Quick flashing red

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbg 150 pTbg 210 p

Tabla de contenido