First Time Power-Up and Start-Up
5.2.3 Control Type V V W (P202 = 5)
Seq
Display Indication/Action
1
Initialization mode
Press key
to enter the first level of the
parameterization mode
3
If necessary, change the content of "P296 – Line
Rated Voltage" (only for 400 V Line)
Press the key
until selecting parameter P002
5
Press key
to save the change of P202
Use key
to select parameter P399
7
If necessary, change the content of "P400 - Motor
Rated Voltage"
Press key
for the next parameter
9
If necessary, change the content of "P402 - Motor
Rated Speed"
Press key
for the next parameter
11
If necessary, change the content of "P404 - Motor
Rated Power"
Press key
for the next parameter
13
If necessary to make the self-tuning, change the
value of P408 to "I"
15
When the self-tuning is completed, it will return to
the (comp) Initialization Mode
32 | CFW300
Seq
2
4
6
8
10
12
14
16
Figure 5.4: Sequence for V V W control
Display Indication/Action
Press keys
or
to select parameter P296
Press key
to change the content of "P202 -
Type of Control" for P202 = 5 (V V W ). Use key
If necessary, change the content of "P399 - Motor
Rated Efficiency" according to the nameplate
Press key
for the next parameter
If necessary, change the content of "P401 - Motor
Rated Current"
Press key
for the next parameter
If necessary, change the content of "P403 - Motor
Rated Frequency"
Press key
for the next parameter
If necessary, change the content of "P407 - Motor
Rated Power factor"
Press key
for the next parameter
During the self-tuning, the HMI will show "Auto",
and the bar will indicate the operation progress
If necessary, change the content of "P409 - Stator
Resistance"