Dräger Polytron 8000 Serie Instructions For Use página 39

Ocultar thumbs Ver también para Polytron 8000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

NOTICE
Sensor failure
The sensor cannot be used for Oxygen measurements in the
presence of Helium!
► Do not use the sensor for Oxygen measurements in the
presence of Helium.
CAUTION
Sensor failure
The exposure to higher concentrations of unsaturated
hydrocarbons, alcohols or hydrogen over an extended period
of time (dose approx. 100,000 ppm x hours) could cause the
sensor to fail.
► Ensure that the sensor is not exposed to such
concentrations over an extended period of time.
Response time
t
0...20
0-5 Vol% O
2
≤ 14 seconds
0-25 Vol% O
≤ 10 seconds
2
1) Response time is higher than the permissible limit of EN 50104.
Stabilization time: 5 x t
0...90
Measuring range
0-5...25 Vol% O
, 0-25 Vol% O
2
Default: 25 Vol% O
2
Minimum reading: -1.25 Vol% O
Warm-up time
Operation: ≤ 20 minutes / Calibration: ≤ 6 hours
19.4 FM Performance Approval for
DrägerSensor H
The DrägerSensor H
S and H
2
diffusion sensors measuring hydrogen sulfide (H
ambient air.
DrägerSensor H
S (6810435)
2
Examination Type P8100
1)
Interface
Environmental parameters
Humidity
Temperature
Storage temperature
2)
Enclosure protection
Range
Accuracy (whichever is
greater)
Accessories
Dräger Polytron
t
0...90
1)
≤ 45 seconds
≤ 27 seconds
2
2
S and H
S LC
2
2
S LC are electrochemical
2
S) in
2
ETR 0400, 0401, 0500, 0501
4-20mA, relay
5 to 95%RH, non-condensing
-40/+65°C (-40/149°F)
0/+40°C (32/104°F)
IP 65/66/67
0-100ppm
measurement uncertainly (of
meas. value) ≤ ±3 % or mini-
mum ≤ ±0.5ppm
®
8000 Series
DrägerSensor H
S (6810435)
2
Dust filter
Adapter kit
Standard
1) HART communication shall not be used for safety-relevant communi-
cation
2) After submersion and jet water the sensor shall be replaced
DrägerSensor H
S LC (6809610)
2
Examination Type P8100
1)
Interface
Environmental parameters
Humidity
Temperature
Storage temperature
2)
Enclosure protection
Range
Accuracy (whichever is
greater)
Accessories
Dust filter
Adapter kit
Standard
1) HART communication shall not be used for safety-relevant communi-
cation
2) After submersion and jet water the sensor shall be replaced
Performance Approvals
6812223
6810536
ANSI/ISA-92.00.01FM6340
ETR 0400, 0401, 0500, 0501
4-20mA, relay
5 to 95%RH, non-condensing
-20/+65°C (-4/149°F)
0/+40°C (32/104°F)
IP 65/66/67
0-100ppm
measurement uncertainly (of
meas.value) ≤ ±3 % or mini-
mum ≤ ±0.5ppm in the range
>50ppm, ±10 % or ±3ppm
6812223
6810536
ANSI/ISA-92.00.01FM6340
en

Publicidad

Tabla de contenido
loading

Tabla de contenido