Thermal Relay Adjustment; Measuring The Ionisation Current - Riello RS BLU Serie Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.11

Thermal relay adjustment

The thermal relay serves to avoid damage to the motor due to an
excessive absorption increase or if a phase is missing.
For calibration, refer to the table in the circuit diagram.
The protection is in any case ensured even if the minimum value of
the thermal relay scale is over the rating absorption of the motor.
This occurs when the motor power supply is 400 V. To reset, in case
of an intervention of the thermal relay, press button 1)(Fig. 23).
5.12

Measuring the ionisation current

The burner is fitted with an ionisation system to check that a
flame is present.
The minimum current for control box operation is 4 µA. The burn-
er provides a much higher current, so controls are not normally
required.
However, if it is necessary to measure the ionisation current, dis-
connect the plug-socket on the ionisation probe cable and insert a
direct current microammeter with a base scale of 100 µA (Fig. 24).
Carefully check the polarities!
Installation
D8267
25
GB
1
Fig. 23
D8154
Fig. 24
20040563
2

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Rs 55/e blu20038488200384912003848920038492

Tabla de contenido