Absolute magnetic encoder system
7
IO-Link Smart Sensor Profile Ed. 2 (BML SL1-ALZ1-UE/MZZ-_U1L-...) (continued)
7.5.4

Output configuration

Both outputs of the BML can be configured.
Index
Subindex
Output Type
1
0x00B4 (180)
2
Tab. 7-11: Output configuration
7.5.5

Diagnostics suppression

If running diagnostics functions in the application causes
problems, the functions can be suppressed.
For diagnostic events implemented in the BML see Event
list on page 39.
Index
Subindex
Diagnosis
1
Suppression
Configuration
0x00F8 (248)
2
Tab. 7-12: Diagnostics suppression
www.balluff.com
Name
Size
Out 1
1 byte
Out 2
1 byte
Name
Size
Suppression Level
1 byte
PD Invalid Suppression
1 byte
Access
Values
Read/Write 0 = Deactivated (default)
1 = PNP
2 = NPN
3 = Push-Pull
Read/Write 0 = Deactivated (default)
1 = PNP
2 = NPN
3 = Push-Pull
Access
Values
Read/Write 0 = All events active (default)
1 = Messages suppressed
2 = Messages and warnings suppressed
3 = All events suppressed
Read/Write 0 = PD Invalid active
1 = PD Invalid suppressed