Electrical Installation - Omron V1000 Guía Rápida De Referencia

Ocultar thumbs Ver también para V1000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 64
3

Electrical Installation

The figure below shows the main and control circuit wiring.
For 1-phase
power supply use
R/L1 and S/L2
Fuses
L1
Power
L2
Supply
L3
Main
Switch
Forward/Stop
Reverse/Stop
External Fault
Fault Reset
Multi-speed 1
Multi-speed 2
Multi-function
digital inputs
(default setting)
2 kΩ
Multi- function pulse / analog inputs
(default: frequency reference)
Safe Disable
inputs
I67E-EN
V1000 Quick Start Guide
DC reactor
(option)
Link
+2
+1
R/L1
V1000
S/L2
Filter
T/L3
S1
S2
S3
S4
S5
S6
+24 V 8 mA
SINK
DIP
switch S3
SOURCE
SC
Shielded ground
terminal
Pulse Input
RP
(max. 32kHz)
Analog input power supply
+V
+10.5 Vdc, max. 20 mA
A1
Multi-function analog input 1
0 to 10 V (20 k
A2
Multi-function analog input 2
0 to 10 V (20 k
AC
0/4 to 20 mA (250
Terminal resistance
(120
H2
H1
HC
Symbols:
Use twisted pair cables
Use shielded twisted pair cables
3 Electrical Installation
Braking
Thermal
resistor
relay
(opt)
B1
B2
U/T1
V/T2
W/T3
Shielded
Cable
Ground
MA
MB
Fault
24 V
MC
P1
During run
0 V
P2
Frequency agree
Photocoupler
PC
common
MP
Pulse train output
(max. 32 kHz)
(Output frequency)
)
AM
Analog output
) or
0 to +10 Vdc (2mA)
)
AC
(Output frequency)
, 1/2 W)
R+
R−
S+
S−
IG
Indicates a main circuit terminal
Indicates a control circuit terminal.
U
V
M
W
Multi-function relay output
250 Vac / 30 Vdc (10 mA to 1A)
(default setting)
Multi-function photo-
coupler output
48 Vdc, max. 50 mA
(default setting)
Monitor outputs
(default setting)
Memobus comm.
RS-485/422
max. 115 kBps
9

Hide quick links:

Publicidad

Tabla de contenido
loading